Siemens
01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6ES7355-2CH00-0AE0

6ES7355-2SH00-0AE0

TEMPERATURE CONTROL MOD. FM355-2C

SIMATIC S7-300, TEMPERATURE

Supply voltage

Load voltage L+

  • Rated value (DC)

24V

24V

  • permissible range, lower limit (DC)

20.4V

20.4V

  • permissible range, upper limit (DC)

28.8V

28.8V

Input current

from load voltage L+ (without load), max.

310mA; Typ. 260 mA

270mA; typ. 220 mA

from backplane bus 5 V DC, max.

75mA; typ. 50 mA

75mA; typ. 50 mA

Power loss

Power loss, typ.

6.5W

5.5W

Power loss, max.

7.8W

6.9W

Digital inputs

Number of digital inputs

8

8

Input characteristic curve in accordance with IEC 61131, type 2

Yes

Yes

Input voltage

  • Rated value (DC)

24V

24V

  • for signal "0"

-3 to +5V

-3 to +5V

  • for signal "1"

13 to 30V

13 to 30V

Input current

  • for signal "1", typ.

7mA

7mA

Cable length

  • shielded, max.

1000m

1000m

  • unshielded, max.

600m

600m

Digital outputs

Number of digital outputs

8

Short-circuit protection

Yes; Electronic

Limitation of inductive shutdown voltage to

L+ (-1.5 V)

Controlling a digital input

Yes

Switching capacity of the outputs

  • on lamp load, max.

5W

Load resistance range

  • lower limit

240Ω

  • upper limit

4kΩ

Output voltage

  • for signal "1", min.

L+ (-2.5 V)

Output current

  • for signal "1" rated value

0.1A

  • for signal "1" permissible range for 0 to 60 C, min.

5mA

  • for signal "1" permissible range for 0 to 60 C, max.

150mA

  • for signal "0" residual current, max.

0.5mA

Parallel switching of two outputs

  • for logic links

Yes

Switching frequency

  • with resistive load, max.

100Hz

  • with inductive load, max.

0.5Hz

  • on lamp load, max.

100Hz

Total current of the outputs (per group)

all mounting positions

  • up to 60 C, max.

400mA

Cable length

  • shielded, max.

1000m

  • unshielded, max.

600m

Analog inputs

Number of analog inputs

4

4

permissible input voltage for voltage input (destruction limit), max.

20V

20V

permissible input current for current input (destruction limit), max.

40mA

40mA

Input ranges

  • Voltage

Yes

Yes

  • Current

Yes

Yes

  • Thermocouple

Yes

Yes

  • Resistance thermometer

Yes

Yes

Input ranges (rated values), voltages

  • 0 to +10 V

Yes

Yes

  • Input resistance (0 to 10 V)

100kΩ

100kΩ

  • -1.75 V to +11.75 V

Yes

Yes

  • Input resistance (-1.75 V to +11.75 V)

100kΩ

100kΩ

Input ranges (rated values), currents

  • 0 to 20 mA

Yes

Yes

  • Input resistance (0 to 20 mA)

50Ω

50Ω

  • 0 to 23.5 mA

Yes

Yes

  • Input resistance (0 to 23.5 mA)

50Ω

50Ω

  • -3.5 mA to +23.5 mA

Yes

Yes

  • Input resistance (-3.5 mA to +23.5 mA)

50Ω

50Ω

  • 4 mA to 20 mA

Yes

Yes

  • Input resistance (4 mA to 20 mA)

50Ω

50Ω

Input ranges (rated values), thermocouples

  • Type B

Yes

Yes

  • Input resistance (Type B)

10MΩ

10MΩ

  • Type E

Yes

Yes

  • Input resistance (Type E)

10MΩ

10MΩ

  • Type J

Yes

Yes

  • Input resistance (type J)

10MΩ

10MΩ

  • Type K

Yes

Yes

  • Input resistance (Type K)

10MΩ

10MΩ

  • Type R

Yes

Yes

  • Input resistance (Type R)

10MΩ

10MΩ

  • Type S

Yes

Yes

  • Input resistance (Type S)

10MΩ

10MΩ

Input ranges (rated values), resistance thermometer

  • Pt 100

Yes

Yes

  • Input resistance (Pt 100)

10MΩ

10MΩ

Thermocouple (TC)

Temperature compensation

  • internal temperature compensation

Yes

Yes

  • external temperature compensation with Pt100

Yes

Yes

Characteristic linearization

  • parameterizable

Yes

Yes

  • for thermocouples

Type B, E, J, K, R, S

Type B, E, J, K, R, S

  • for resistance thermometer

Pt100 (standard)

Pt100 (standard)

Cable length

  • shielded, max.

200m; 50 m at 80 mV and thermocouples

200m; 50 m at 80 mV and thermocouples

Analog outputs

Number of analog outputs

4

Voltage output, short-circuit protection

Yes

Voltage output, short-circuit current, max.

25mA

Current output, no-load voltage, max.

18V

Output ranges, voltage

  • 0 to 10 V

Yes

  • -10 V to +10 V

Yes

Output ranges, current

  • 0 to 20 mA

Yes

  • 4 mA to 20 mA

Yes

Connection of actuators

  • for voltage output two-wire connection

Yes

  • for current output two-wire connection

Yes

Load impedance (in rated range of output)

  • with voltage outputs, min.

1kΩ

  • with voltage outputs, capacitive load, max.

1F

  • with current outputs, max.

500Ω

  • with current outputs, inductive load, max.

1mH

Cable length

  • shielded, max.

200m; 50 m at 80 mV and thermocouples

Analog value generation for the inputs

Measurement principle

integrating

integrating

Integration and conversion time/resolution per channel

  • Resolution with overrange (bit including sign), max.

14bit

14bit

  • Conversion time (per channel)

100ms; At 50/60 Hz

100ms; At 50/60 Hz

Analog value generation for the outputs

Settling time

  • for resistive load

0.1ms

  • for capacitive load

3.3ms

  • for inductive load

0.5ms

Encoder

Connection of signal encoders

  • for voltage measurement

Yes

Yes

  • for current measurement as 4-wire transducer

Yes

Yes

Connectable encoders

  • 2-wire sensor

Yes

Yes

  • permissible quiescent current (2-wire sensor), max.

1.5mA

1.5mA

Errors/accuracies

Linearity error (relative to input range), (+/-)

0.05%

0.05%

Temperature error (relative to input range), (+/-)

0.005%/K

0.005%/K

Linearity error (relative to output range), (+/-)

0.05%

Temperature error (relative to output range), (+/-)

0.02%/K

Operational error limit in overall temperature range

  • Voltage, relative to input range, (+/-)

0.6%; 0.6 to 0.7 %

0.06%; 0.06 to 0.7%

  • Current, relative to input range, (+/-)

0.6%; 0.6 to 0.7 %

0.06%; 0.06 to 0.7%

  • Resistance thermometer, relative to input range, (+/-)

0.6%; 0.6 to 0.7 %

0.06%; 0.06 to 0.7%

  • Voltage, relative to output range, (+/-)

0.5%

  • Current, relative to output range, (+/-)

0.6%

Basic error limit (operational limit at 25 C)

  • Voltage, relative to input range, (+/-)

0.04%; 0.04 to 0.5 %

0.04%; 0.04 to 0.5 %

  • Current, relative to input range, (+/-)

0.04%; 0.04 to 0.5 %

0.04%; 0.04 to 0.5 %

  • Resistance thermometer, relative to input range, (+/-)

0.04%; 0.04 to 0.5 %

0.04%; 0.04 to 0.5 %

  • Voltage, relative to output range, (+/-)

0.4%

  • Current, relative to output range, (+/-)

0.5%

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

  • Series mode interference (peak value of interference < rated value of input range), min.

40dB

40dB

  • Common mode interference (USS < 2.5 V) , min.

70dB

70dB

Interrupts/diagnostics/status information

Substitute values connectable

Yes; Parameterizable

Yes; Parameterizable

Integrated Functions

Control technology

  • Number of closed-loop controllers

4

4

Potential separation

Potential separation controller

  • between the channels

No

No

  • between the channels and backplane bus

Yes; Optocoupler

Yes; Optocoupler

Permissible potential difference

Between the inputs and MANA (UCM)

2.5 V DC

2.5 V DC

Isolation

Isolation tested with

500 V DC

500 V DC

Connection method

required front connector

2x 20-pin

2x 20-pin

Dimensions

Width

80mm

80mm

Height

125mm

125mm

Depth

120mm

120mm

Weights

Weight, approx.

470g

470g


















2018
Siemens Industry Catalog Drive technology Automation technology Automation systems SIMATIC Industrial Automation Systems Controllers I/O systems SIMATIC ET 200 systems for the control cabinet SIMATIC ET 200SP SIMATIC ET 200MP SIMATIC ET 200S SIMATIC ET 200M Interface modules SIPLUS Interface modules I/O modules Digital modules Analog modules Analog modules with HART F digital/analog modules Ex digital modules Ex analog modules Function modules FM 350-1 counter module FM 350-2 counter module FM 351 positioning module FM 352 cam controllers FM 352-5 high-speed Boolean processor FM 353 positioning module FM 354 positioning module FM 355 controller module FM 355-2 temperature controller module SM 338 POS input module SIPLUS function modules Special modules Communication Connection system Power supplies SIMATIC ET 200iSP SIMATIC ET 200 systems without control cabinet IO systems for heating elements PROFIBUS components PROFINET components Network components for PROFIBUS Network transitions SIMATIC control systems Software for SIMATIC Controllers Programming devices Siemens Partner Programm SIMOTION Motion Control System SINUMERIK CNC automation systems System cabling/control cabinets Operator control and monitoring systems SIMATIC HMI Identification systems Industrial communication Industrial controls Industry software PC-based Automation Process control systems Process instrumentation Process analytics SITOP power supply Products for specific requirements Energy Building Technologies Low-Voltage controls and distribution Safety Systems - Safety Integrated Market-specific solutions Industry Services Software ... and everything else you need




  © " " 2007-2022
  (4872) 700-366  skenergo@mail.ru
.