Order No. | 6GK7? 342-5DA02-0XE0 |
Product type designation | CP?342-5 |
Transmission rate | |
Transmission rate at interface 1 in accordance with PROFIBUS | 9.6 Kbit/s … 12 Mbit/s |
Interfaces | |
Number of electrical connections | |
- at interface 1 in accordance with PROFIBUS
| 1 |
| 1 |
Design of electrical connection | |
- at interface 1 in accordance with PROFIBUS
| 9-pin D-sub socket (RS485) |
| 4-pin terminal strip |
Supply voltage, current consumption, power loss | |
Type of power supply | DC |
Power supply | |
| 5 V |
| 24 V |
Relative positive tolerance at 24 V DC | 20 % |
Relative negative tolerance at 24 V DC | 15 % |
Current consumed | |
- from backplane bus at 5 V DC, typical
| 0.15 A |
- from external power supply with 24 V DC
| |
| 0.25 A |
| - |
Effective power loss | 5 W |
Permitted ambient conditions | |
Ambient temperature | |
| 0 … 60 °C |
| -40 … +70 °C |
| -40 … +70 °C |
| - |
Relative humidity at 25 °C without condensation during operation, maximum | 95 % |
IP degree of protection | IP20 |
Design, dimensions and weights | |
Module format | S7-300 compact module, single-width |
Width | 40 mm |
Height | 125 mm |
Depth | 120 mm |
Net weight | 0.3 kg |
Product properties, functions, components?General | |
Number of modules | |
| 4 |
| - |
Performance data | |
Performance data?Open communication | |
Number of possible connections for open communication by means of SEND/RECEIVE blocks, maximum | 16 |
Data volume as user data per connection for open communication by means of SEND/RECEIVE blocks, maximum | 240 byte |
Performance data? PROFIBUS? DP | |
Service as DP master DPV0 | Yes |
Number of DP slaves operable on DP master | 124 |
Data volume | |
- of address area of inputs as DP master, total
| 2 160 byte |
- of address area of outputs as DP master, total
| 2 160 byte |
- of address area of inputs per DP slave
| 244 byte |
- of address area of outputs per DP slave
| 244 byte |
- of address area of diagnostics data per DP slave
| 240 byte |
Service as DP slave | |
| Yes |
| No |
Data volume | |
- of address area of inputs as DP slave, total
| 240 byte |
- of address area of outputs as DP slave, total
| 240 byte |
Performance data?S7 communication | |
Number of possible connections for S7 communication | |
| 16 |
- For PG connections, maximum
| - |
- For PG/OP connections, maximum
| - |
| - |
Performance data?Multiprotocol operation | |
Number of active connections in multiprotocol mode | |
| 32 |
| 28 |
Product functions?Management, configuration, programming | |
Configuration software required | STEP?7?V5.1 SP2 or higher |