Connection of SIMATIC S7-300/SINUMERIK 840D powerline to Industrial Ethernet
2 x RJ45 interface for 10/100 Mbit/s full/half-duplex connection with auto-sensing/auto-negotiation and auto-crossover function
Integrated 2-port real-time switch ERTEC
Multi-protocol operation with ISO, TCP, UDP transport protocol and PROFINET IO
Adjustable keep-alive function
Communications services:
Open communication (ISO, TCP/IP, and UDP)
PROFINET IO-Controller or PROFINET IO-Device
PG/OP communication: Cross-network by means of S7 routing
S7 communication (client, server, multiplexing)
Media redundancy (MRP); within an Ethernet network with ring topology, the CP supports the media redundancy procedure MRP (V2.2 or higher).
Multicast for UDP
IP address assignment via DHCP, simple PC tool or via the user program (e.g. HMI)
Access protection via configurable access list
Remote programming and commissioning via Industrial Ethernet
Configuration with STEP 7
Automatic setting of CPU clock setting over Ethernet with NTP or SIMATIC procedure
Web diagnostics
Integration in network management systems via SNMP (MIB2 diagnostics information)
Diagnostics possibilities in STEP 7 and via web browser
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
SIPLUS CP 343-1
Article No.
6AG1343-1EX30-7XE0
BasedOn Article No.
6GK7343-1EX30-0XE0
Ambient temperature range
-25 ... +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies except for the ambient conditions.
Ambient conditions
Relative humidity
100%, condensation/frost permissible. No commissioning if condensation present.
Biologically active substances, compliance with EN 60721-3-3
Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!
Chemically active substances, compliance with EN 60721-3-3
Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation!
Mechanically active substances, compliance with EN 60721-3-3
Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation!
Air pressure (depending on the highest positive temperature range specified)
1 080 ... 795 hPa (-1 000 ... +2 000 m) see ambient temperature range
795 ... 658 hPa (+2000 ... +3500 m) derating 10 K
658 ... 540 hPa (+3 500 ... +5 000 m) derating 20 K
For further technical documentation on SIPLUS, see: