Unless explicitly specified otherwise, the following technical specifications are valid for all SINAMICS G110D distributed inverters.
General technical specifications
Mechanical specifications
Vibratory load
Transport acc. to EN 60721?3?2 1)
Class 1M2
Operation acc. to EN 60721?3?3
Class 3M2
Shock load
Transport acc. to EN 60721?3?2 1)
Class 1M2
Operation acc. to EN 60721?3?3
Class 3M2
Ambient conditions
Degree of protection
IP65/UL Type 3
Protection class
According to EN 61800?5?1
Class III (PELV)
Touch protection
According to EN 61800?5?1
Class I (with protective conductor system)
Humidity, max.
95 % at 40 °C (104 °F)
Ambient temperature
Storage 1) acc. to EN 60068?2?1
-40 ... +70 °C (-40 ... +158 °F)
Transport 1) acc. to EN 60068-2-1
-40 ... +70 °C (-40 ... +158 °F)
Operation acc. to EN 60068?2?2
-10 ... +40 °C (14 ... +104 °F) without derating >40 ... 55 °C (104 ... +131 °F), see derating characteristics
Environmental class/harmful chemical substances
Operation acc. to EN 60721?3?3
Class 3C2
Degree of pollution
According to EN 61800?5?1
2
Standards
Compliance with standards
UL 508C (UL list number E121068), CE, C-Tick
CE marking, according to
Low-Voltage Directive 2006/95/EC
EMC Directive 2)
Frame sizes FSA to FSC with integrated line filter class A
Category C2 3) according to EN 61800?3
Note:
The EMC product standard EN 61800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter. The frequency inverters on their own do not generally require identification according to the EMC Directive.
1) In product packaging.
2) For further general information see also chapter SINAMICS G120, Technical specifications, Compliance with standards.
3) With shielded motor cable up to 15 m (49 ft).
Technical specifications, control electronics
Electrical specifications
Operating voltage
External 24 V DC necessary
Current consumption, max. 1)
(from the non-switched 24 V DC supply, yellow AS-Interface cable)
320 mA
Current consumption, max.
(from the switched 24 V DC supply, black AS-Interface cable)
Without supplementary fan
180 mA
With supplementary fan
350 mA
Fixed frequencies
6, parameterizable
Interfaces
Digital inputs
4
Analog inputs
(0 ... 10 V)
1
Bus interface
AS-Interface
PTC/KTY interface
Connection via Power Modules
Motor temperature sensor
1 input, sensors that can be connected: PTC, KTY or bimetal
Control of a mechanical motor brake
Connection via Power Modules
Memory card slot
Optional
RS232 interface
Connection with RS232 interface cable via the optical inverter interface
USB interface
Connection with USB interface cable via the optical inverter interface
Open-loop/closed-loop control technique and software
V/f linear/quadratic/parameterizable
?
V/f with flux current control (FCC)
?
Software functions
Signal interconnection with BICO technology
Automatic restart after line supply failure or operational fault
Slip compensation
Free function blocks (FFB) for logical operations
Ramp smoothing
3 selectable drive data sets
3 selectable command data sets (CDS) (manual/auto)
Flying restart
JOG
Technology controller (PID)
Thermal motor protection
Thermal inverter protection
Setpoint input
Motor identification
Motor holding brake
1) Includes the current consumption of connected sensors. Analog input as voltage input, 0 V to 10 V.
General technical specifications, power electronics
System operating voltage
380 ... 500 V AC 3 AC ±10 %
Grid requirement, short-circuit power RSC
No restriction
Input frequency
47 ... 63 Hz
Output frequency
Control mode V/f
0 ... 550 Hz1)
Pulse frequency
4 kHz (standard), for higher pulse frequencies up to 16 kHz, see derating data
Power factor ?
0.7 ... 0.85
Inverter efficiency ?
95%
Output voltage, max.
as % of input voltage
0 ... 87%
Overload capability
High overload (HO)
Average maximum rated output current during a cycle time of 300 s
1.5 ? rated output current (i.e. 150 % overload) over 60 s at a cycle time of 300 s
2 ? rated output current (i.e. 200 % overload) over 3 s at a cycle time of 300 s
Electromagnetic compatibility
Integrated class A line filter according to EN 55011
Possible braking methods
DC braking Integrated brake control supplies DC power supply for the brake
Line voltage
380 V AC
400 V AC
440 V AC
480 V AC
500 V AC
Rectified brake voltage
171 V DC
180 V DC
198 V DC
216 V DC
225 V DC
Recommended brake coil voltage for Siemens motors
170 ... 200 V DC
170 ... 200 V DC
184 ... 218 V DC 2)
184 ... 218 V DC 2)
184 ... 218 V DC 2)
-
Disconnection on the DC side permits "fast" braking.
Output current, max.
600 mA (with UL approval)
1 A (without UL approval)
Permissible mounting position
Horizontal wall mounting and mounting in the horizontal position
Relative humidity
<95 % RH, condensation not permissible
Cooling
FSA: Convection
FSB and FSC: Air cooling as required using the integrated fan
Installation altitude
Up to 1000 m (3281 ft) above sea level without derating
3) The input current depends on the motor load and line impedance. The input currents apply for load at rated power for a line impedance corresponding to uK = 1 %.