Wide power range from 0.75 kW to 7.5 kW (1.0 hp to 10 hp)
Fast commissioning and maintenance as well as extended diagnostic functions and communications capability with AS-Interface according to specification 3.0:
Reduced number of interfaces
Plant-wide engineering
Easy to handle
Mechanical design, installation and retrofit of systems are significantly simplified as a result of the compact and space-saving design with an extremely low profile and with the same drilling dimensions for all power ratings; further, the dimensions are identical with those of the SINAMICS G120D inverter.
Easy commissioning and maintenance as a result of the same, standardized connectors for the bus, power and I/O connections (ISO 23570) for the complete range of power ratings of SINAMICS G110D and SINAMICS G120D.
The same connectors are used as for the SIRIUS M200D motor starter
Simple, standard implementation of completely distributed plant and system concepts by using products in a scalable fashion:
SIRIUS M200D (motor starter)
SINAMICS G110D (inverter for basic conveyor-related applications)
SINAMICS G110M (inverter for conveyor-related applications)
SIMATIC ET 200pro FC?2 (inverter for distributed I/O)
SINAMICS G120D (inverter for demanding conveyor-related applications)
High degree of operator friendliness by using the Intelligent Operator Panel (IOP) to parameterize, diagnose, control (open-loop) and copy drive parameters in the BOP
Easy to replace thanks to a plug-in design and the use of a memory card, providing the highest degree of service friendliness
Simple connection, engineering, data management as well as control of the inverter in sophisticated plants and systems as a result of the consequential integration in TIA (Totally Integrated Automation)
Using the optional maintenance switch, the inverter can be simply disconnected from the line supply when service is required, without any additional components or without additional wiring costs when configuring the system
Using the optional manual local control, commissioning is fast and can be limited to specific areas, the application can be manually pre-tested on site and the system can be cleared or emptied without requiring comprehensive options.
By being able to connect up to 5 sensors directly at the unit, practically all of the drive-relevant information can be directly managed; local pre-processing of the signals takes the load off the fieldbus and ensures a fast and reproducible response time
Integrated EMC filter class A (acc. to EN 55011)
Integrated brake control, brake voltages supported: 180 V DC and 205 V DC
Integrated motor protection using a thermal motor model and evaluation of PTC, KTY or bimetal temperature sensors
Easy replacement of devices and fast copying of parameters to the memory card using the optional memory card holder and the optional memory card
Engineering and commissioning with standard engineering tools such as SIZER for Siemens Drives (V3.2 and higher), STARTER (V4.1.3 and higher) and Drive ES ensure fast engineering and simple commissioning - STARTER is integrated into STEP 7 with Drive ES Basic, with all the advantages of central data storage and totally integrated communication
Software parameters for simple adaptation to 50 Hz or 60 Hz motors (IEC or NEMA motors)
Increased degree of ruggedness and longer service life as the electronic modules are coated