Unless explicitly specified otherwise, the following technical specifications are valid for all SINAMICS G110D distributed inverters. General technical specifications |
|---|
Mechanical specifications | Vibratory load | | - Transport acc. to EN 60721‑3‑2 1)
| Class 1M2 | - Operation acc. to EN 60721‑3‑3
| Class 3M2 | Shock load | | - Transport acc. to EN 60721‑3‑2 1)
| Class 1M2 | - Operation acc. to EN 60721‑3‑3
| Class 3M2 | Ambient conditions | Degree of protection | IP65/UL Type 3 | Protection class According to EN 61800‑5‑1 | Class III (PELV) | Touch protection According to EN 61800‑5‑1 | Class I (with protective conductor system) | Humidity, max. | 95 % at 40 °C (104 °F) | Ambient temperature | | - Storage 1) acc. to EN 60068‑2‑1
| -40 ... +70 °C (-40 ... +158 °F) | - Transport 1) acc. to EN 60068-2-1
| -40 ... +70 °C (-40 ... +158 °F) | - Operation acc. to EN 60068‑2‑2
| -10 ... +40 °C (14 ... +104 °F) without derating >40 ... 55 °C (104 ... +131 °F), see derating characteristics | Environmental class/harmful chemical substances | | - Operation acc. to EN 60721‑3‑3
| Class 3C2 | Degree of pollution According to EN 61800‑5‑1 | 2 | Standards | Compliance with standards | UL 508C (UL list number E121068), CE, RCM | CE marking, according to | Low Voltage Directive 2014/35/EU | EMC Directive | | - Frame sizes FSA to FSC with integrated line filter class A
| Category C2 2) according to EN 61800‑3 | | Note: The EMC product standard EN 61800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter. The frequency inverters on their own do not generally require identification according to the EMC Directive. |
1) In product packaging. 2) With shielded motor cable up to 15 m (49 ft). Technical specifications, control electronics |
|---|
Electrical specifications | Operating voltage | External 24 V DC necessary | Current consumption, max. 1) (from the non-switched 24 V DC supply, yellow AS-Interface cable) | 320 mA | Current consumption, max. (from the switched 24 V DC supply, black AS-Interface cable) | | - Without supplementary fan
| 180 mA | | 350 mA | Fixed frequencies | 6, parameterizable | Interfaces | Digital inputs | 4 | Analog inputs (0 ... 10 V) | 1 | Bus interface | AS-Interface | PTC/KTY interface | Connection via Power Modules | | 1 input, sensors that can be connected: PTC, KTY, bimetal or Pt1000 | Control of a mechanical motor brake | Connection via Power Modules | Memory card slot | Optional | RS232 interface | Connection with RS232 interface cable via the optical inverter interface | USB interface | Connection with USB interface cable via the optical inverter interface | Open-loop/closed-loop control techniques and software | V/f linear/quadratic/parameterizable | ✓ | V/f with flux current control (FCC) | ✓ | Software functions | - Signal interconnection with BICO technology
- Automatic restart after line supply failure or operational fault
- Slip compensation
- Free function blocks (FFB) for logical operations
- Ramp smoothing
- 3 selectable drive data sets
- 3 selectable command data sets (CDS) (manual/auto)
- Flying restart
- JOG
- Technology controller (PID)
- Thermal motor protection
- Thermal inverter protection
- Setpoint input
- Motor identification
- Motor holding brake
|
1) Includes the current consumption of connected sensors. Analog input as voltage input, 0 V to 10 V. General technical specifications, power electronics |
|---|
System operating voltage | 380 ... 500 V AC 3 AC ±10 % | Line supply requirements Short-circuit power ratio RSC | No restriction | Input frequency | 47 ... 63 Hz | Output frequency | | | 0 ... 550 Hz1) | Pulse frequency | 4 kHz (standard), for higher pulse frequencies up to 16 kHz, see derating data | Power factor λ | 0.7 ... 0.85 | Inverter efficiency η | 95 % | Output voltage, max. as % of input voltage | 0 ... 87 % | Overload capability | | | - Average maximum rated output current during a cycle time of 300 s
- 1.5 × rated output current (i.e. 150 % overload) over 60 s at a cycle time of 300 s
- 2 × rated output current (i.e. 200 % overload) over 3 s at a cycle time of 300 s
| Electromagnetic compatibility | Integrated class A line filter according to EN 55011 | Possible braking methods | DC braking Integrated brake control supplies DC power supply for the brake | Line voltage | 380 V AC | 400 V AC | 440 V AC | 480 V AC | 500 V AC | Rectified brake voltage | 171 V DC | 180 V DC | 198 V DC | 216 V DC | 225 V DC | Recommended brake coil voltage for Siemens motors | 170 ... 200 V DC | 170 ... 200 V DC 184 ... 218 V DC 2) | 184 ... 218 V DC 2) | 184 ... 218 V DC 2) | - | Disconnection on the DC side permits "fast" braking. | | - 600 mA (with UL approval)
- 1 A (without UL approval)
| Permissible mounting position | Horizontal wall mounting and mounting in the horizontal position | Relative humidity | <95 % RH, condensation not permissible | Cooling | - FSA: Convection
- FSB and FSC: Air cooling as required using the integrated fan
| Installation altitude | - Up to 1000 m (3281 ft) above sea level without derating
- >1000 m (3281 ft) see derating characteristics
| Short-Circuit Current Rating SCCR 3) | 40 kA | Protection functions | - Undervoltage
- Overvoltage
- Overload
- Ground fault
- Short-circuit
- Stall protection
- Motor blocking protection
- Motor overtemperature
- Inverter overtemperature
- Parameter locking
| Compliance with standards | UL 508C (UL list number E121068), CE, RCM | CE marking, according to | Low Voltage Directive 2014/35/EU |
1) For further information, see https://support.industry.siemens.com/cs/document/107669667 2) With voltage boost activated. 3) Applies to industrial control panel installations to NEC article 409 or UL 508A. Line voltage 380 ... 500 V 3 AC | SINAMICS G110D |
|---|
| 6SL3511-.PE17-5AM0 | 6SL3511-.PE21-5AM0 | 6SL3511-.PE23-0AM0 | 6SL3511-.PE24-0AM0 | 6SL3511-.PE25-5AM0 | 6SL3511-.PE27-5AM0 |
|---|
Rated output current Irated1) | A | 2.3 | 4.3 | 7.7 | 10.2 | 13.2 | 19 | Maximum output current Imax | A | 4.6 | 8.6 | 15.4 | 20.4 | 26.4 | 38 | Rated power | kW (hp) | 0.75 (1) | 1.5 (1.54)) | 3 (4) | 4 (5) | 5.5 (7.5) | 7.5 (10) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | 4 | 4 | Efficiency η | % | 95 | 95 | 95 | 95 | 95 | 95 | Power loss 2) At rated output current | kW | 0.044 | 0.068 | 0.105 | 0.168 | 0.196 | 0.261 | Rated input current 3) | A | 2 | 3.8 | 7 | 9.1 | 12.2 | 17.9 | Line supply connection U1/L1, V1/L2, W1/L3, PE | | HAN Q4/2 (connector) | HAN Q4/2 (connector) | HAN Q4/2 (connector) | HAN Q4/2 (connector) | HAN Q4/2 (connector) | HAN Q4/2 (connector) | | mm2 | 1.5 ... 6 | 1.5 ... 6 | 2.5 ... 6 | 2.5 ... 6 | 4 ... 6 | 4 ... 6 | Motor connection U2, V2, W2, PE, motor brake, temperature sensor | | HAN Q8 (socket) | HAN Q8 (socket) | HAN Q8 (socket) | HAN Q8 (socket) | HAN Q8 (socket) | HAN Q8 (socket) | | mm2 | 1 ... 4 | 1 ... 4 | 2.5 ... 4 | 2.5 ... 4 | 4 | 4 | Motor cable length, max. | m (ft) | 15 (49) | 15 (49) | 15 (49) | 15 (49) | 15 (49) | 15 (49) | Degree of protection | | IP65 | IP65 | IP65 | IP65 | IP65 | IP65 | Dimensions | | | | | | | | | mm (in) | 445 (17.52) | 445 (17.52) | 445 (17.52) | 445 (17.52) | 445 (17.52) | 445 (17.52) | | mm (in) | 210 (8.27) | 210 (8.27) | 210 (8.27) | 210 (8.27) | 210 (8.27) | 210 (8.27) | | | | | | | | | - Without maintenance switch
| mm (in) | 125 (4.92) | 125 (4.92) | 125 (4.92) | 165 (6.50) | 240 (9.45) | 240 (9.45) | | mm (in) | 145 (5.71) | 145 (5.71) | 145 (5.71) | 165 (6.50) | 240 (9.45) | 240 (9.45) | Frame size | | FSA | FSA | FSA | FSB | FSC | FSC | Weight, approx. | | | | | | | | - Without maintenance switch
| kg (lb) | 6.7 (14.8) | 6.7 (14.8) | 6.9 (15.2) | 7.4 (16.3) | 9.4 (20.7) | 9.5 (20.9) | | kg (lb) | 7 (15.4) | 7 (15.4) | 7.2 (15.9) | 7.7 (17) | 9.7 (21.4) | 9.8 (21.6) |
1) The rated output current Irated is based on the duty cycle for high overload (HO). 2) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 3) The input current depends on the motor load and line impedance. The input currents apply for load at rated power for a line impedance corresponding to uK = 1 %. 4) It is not possible to make any assignment to a particular standard.
|
|