Guidelines | - EU EMC Guideline 89/336/EEC
- EC low voltage, RL 73/23/EEC
- ATEX directive 94/9/EC
|
Design | Explosion-protected enclosure (Ex e) with viewing window in the cover |
Degree of protection | IP65 |
Terminals | 2.5 mm, finely stranded |
Pressure sensors | - MIN A = 0 … 25 hPa
- MIN B = 0 … 25 hPa
- MAX = 0 … 25 hPa
- MAX 1 = 0 … 25 hPa
- DIFF A = 0 … 25 hPa
- DIFF B = 0 … 25 hPa
|
Prepurging time | 0 … 99 min; 5 sec dropout delayed |
Weight | 10.6 kg |
Electrical data | |
Supply voltage | 230 V AC (115 V AC) ± 10 %, 48 … 62 Hz |
Power consumption | 21 W /230 V |
Relay contacts | K2/3; max. 250 V, 5 A with cos ? = 1, K4/K5; supply voltage or floating, max. 250 V, 5 A with cos ? = 1 |
Communication (for service only) | RS 485 interface |
Temperature switching value (option) | 0 … +40 °C |
Explosion protection | |
Marking | II 2(1)G Ex de ib [ia Ga px] IIC T4 Gb |
Design examination certificate | DMT 99 ATEX E 082 |
Ambient temperature | -20 … +40 °C |