Control unit ATEX II 2G, continuous purging
|
|
|
Guidelines
|
EC EMC directive 89/336/EEC, EC low voltage, RL 73/23/EEC, Ex directive 94/9/EC
|
|
Design
|
Explosion-protected enclosure (EEx e) with viewing window in the cover
|
|
Degree of protection
|
IP65
|
|
Terminals
|
2.5 mm, finely stranded
|
|
Pressure sensors
|
MIN A = 0 … 25 hPa, MIN B = 0 … 25 hPa, MAX = 0 … 25 hPa, MAX 1 = 0 … 25 hPa, DIFF A = 0 … 25 hPa, DIFF B = 0 … 25 hPa
|
|
Prepurging time
|
0 … 99 min; 5 sec dropout delayed
|
|
Weight
|
10 kg
|
|
Electrical data
|
|
|
Supply voltage
|
230 V AC (115 V AC) ± 10%, 48 … 62 Hz
|
|
Power consumption
|
21 W /230 V
|
|
NO contacts
|
K2/3; max. 250 V, 5 A with cos ? = 1,
K4/K5; supply voltage or floating, max. 250 V, 5 A with cos ? = 1
|
|
Communication
|
RS 485 interface
|
|
Temperature switching value (option)
|
0 … +40 °C
|
|
Explosion protection
|
|
|
Marking
|
EEx e d ib [ia p] IIC T4/T6
|
|
Test certification
|
DMT 99 ATEX E 082
|
|
Ambient temperature
|
-20 … +40 °C
|
|
|