Line voltage 380 … 480 V 3 AC | Line Connection Module |
|---|
Type |
|---|
6SL3700-0LE41-3AA3 | 6SL3700-0LE41-6AA3 | 6SL3700-0LE42-0BA3 | 6SL3700-0LE43-2BA3 | 6SL3700-0NE44-0BA3 | 6SL3700-0NE46-3BA3 |
|---|
| | | Prepared for connection to Line Modules connected in parallel |
|---|
Infeed/regenerative feedback current | | | | A | 1250 | 1600 | 2000 | 3200 | 4000 | 6300 | Power requirement | | | - 24 V DC aux. power supply
| A | – | – | – | – | – | – | | A | 1.07 | 1.07 | 2.14 | 2.14 | 4 | 4 | Power loss, max. 1) | | | | | | | kW | 0.29 | 0.41 | 0.6 | 0.95 | 1.8 | 1.8 | | | | | kW | 0.29 | 0.41 | 0.6 | 0.95 | 1.8 | 1.8 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 68/70 | 68/70 | 70/72 | 70/72 | 72/74 | 72/74 | Line supply connection L1, L2, L3 | | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 64/M12 | 64/M12 | - Conductor cross-section, max. (IEC)
| mm2 | 10 Г— 240 | 10 Г— 240 | 10 Г— 240 | 10 Г— 240 | 64 Г— 240 | 64 Г— 240 | PE/GND connection | | PE bar | PE bar | PE bar | PE bar | PE bar | PE bar | | mm2 | 600 | 600 | 600 | 600 | 600 | 600 | - Conductor cross-section, max. (IEC)
| mm2 | 240 | 240 | 240 | 240 | 240 | 240 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | mm | 1000 | 1000 | 1000 | 1000 | 1200 | 1200 | | mm | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | | mm | 600 | 600 | 600 | 600 | 600 | 600 | Weight, approx. | | | | kg | 470 | 490 | 620 | 720 | 1100 | 1100 | Frame size | | JL | JL | KL | LL | – | – |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 2) The cabinet height increases by 250 mm with IP21 degree of protection, and by 400 mm with IP23 degree of protection.
|
|