Selection and ordering dataThe table below lists recommended ratings for input-end switching and fuse protection elements for compliance with IEC standards. Notes for use in compliance with IEC standards: 3NA3 or 3NE1 fuses are recommended for European countries. Notes for use in compliance with UL regulations: UL-approved fuses must be used in North America. Notes regarding installations in Canada: Overvoltage protection devices in accordance with overvoltage category III and with the following ratings must be connected on the line side of the converter: - Rated voltage 480 V/600 V (phase-phase), 480 V/600 V (phase-to-ground) at a rated line voltage of 480 V/600 V
- Voltage limit 4 kV (phase-phase) and 6 kV (phase-ground)
All overvoltage protection devices used must comply with Canadian standards for industrial installations. Additional information about the listed fuses can be found in Catalogs LV 10, IC 10 and IC 10 AO. Rated power 1) | SINAMICS G120 PM330 Power Modules | Main contactor acc. to IEC | Switch disconnector acc. to IEC | Cable protection fuse incl. semiconductor protection2) acc. to IEC | Cable protection fuse acc. to IEC | Cable protection fuse incl. semiconductor protection acc. to UL/cUL |
|---|
400 V/690 V | 460 V/575 V | Type | | | Rated current | | Rated current | Minimum short-circuit current | | Rated current | Minimum short-circuit current | | Rated current | |
|---|
kW | hp | 6SL3310-... | Frame size | Type | A | Type | A | A | Article No. | A | A | Article No. | A | Article No. |
|---|
380 ... 480 V 3 AC | 160 | 200 | 1PE33-0AA0 | GX | 3RT1456 *) | 400 | 3KL5730 | 450 | 3500 | 3NE1333-2 | 400 | 9500 | 3NA3260 | 450 | 3NE1333-2 | 200 | 250 | 1PE33-7AA0 | GX | 3RT1456 *) | 400 | 3KL5730 | 500 | 4500 | 3NE1334-2 | 500 | 14000 | 3NA3365 | 500 | 3NE1334-2 | 250 | 300 | 1PE34-6AA0 | GX | 3RT1456 **) | 630 | 3KL6130 | 560 | 7000 | 3NE1435-2 | 630 | 20000 | 3NA3372 | 560 | 3NE1435-2 | 315 | 400 | 1PE35-8AA0 | HX | 3RT1456 **) | 630 | 3KL6130 | 710 | 10000 | 3NE1437-2 | 710 | 3NE1437-2 | 355 | 450 | 1PE36-6AA0 | HX | 3RT1466 *) | 800 | 3KL6230 | 800 | 11000 | 3NE1438-2 | 800 | 30000 | 3NA3475 | 800 | 3NE1438-2 | 400 | 500 | 1PE37-4AA0 | HX | 3RT1466 **) | 800 | 3KL6230 | 850 | 13000 | 3NE1448-2 | 850 | 3NE1448-2 | 450 | 500 | 1PE38-4AA0 | JX | 3RT1466 **) | 1000 | 3KD5034 | 2 × 500 | 10400 | 3NE1334‑3 *) | 1000 | 40000 | 3NA3480 | 1000 | 3NB3350-1KK26 | 500 | 600 | 1PE38-8AA0 | JX | 3RT1466 **) | 1000 | 3KD5034 | 2 × 560 | 14000 | 3NE1435‑3 *) | 1000 | 40000 | 3NA3480 | 1100 | 3NB3351-1KK26 | 560 | 700 | 1PE41-0AA0 | JX | 3RT1476 *) | 1250 | 3KD5234 | 2 × 630 | 16000 | 3NE1436‑3 *) | 1250 | 52000 | 3NA3482 | 1250 | 3NB3352-1KK26 | 500 ... 690 V 3 AC | 315 | 350 | 1PG33-7AA0 | HX | 3RT1476 | 400 | 3KL5730 | 450 | 3500 | 3NE1333-2 | 400 | 10000 | 3NA3360-6 | 450 | 3NE1333-2 | 355 | 400 | 1PG34-0AA0 | HX | 3RT1476 | 630 | 3KL6130 | 500 | 4500 | 3NE1334-2 | 425 | 10500 | 3NA3362-6 | 500 | 3NE1334-2 | 400 | 450 | 1PG34-5AA0 | HX | 3RT1476 | 630 | 3KL6130 | 560 | 7000 | 3NE1435-2 | 500 | 13000 | 3NA3365-6 | 560 | 3NE1435-2 | 450 | 450 | 1PG35-2AA0 | HX | 3RT1476 | 630 | 3KL6130 | 630 | 8500 | 3NE1436-2 | 2 x 315 | 14600 | 3NA3352‑6 *) | 630 | 3NE1436-2 | 500 | 500 | 1PG35-8AA0 | JX | 3RT1466 **) | 630 | 3KD4634 | 710 | 10000 | 3NE1437-2 | 2 x 355 | 16000 | 3NA3354‑6 *) | 710 | 3NE1437-2 | 560 | 600 | 1PG36-5AA0 | JX | 3RT1466 **) | 800 | 3KD4834 | 800 | 11000 | 3NE1438-2 | 2 x 400 | 20000 | 3NA3360‑6 *) | 800 | 3NE1438-2 | 630 | 700 | 1PG37-2AA0 | JX | 3RT1466 **) | 1000 | 3KD5034 | 850 | 13000 | 3NE1448-2 | 2 x 425 | 21000 | 3NA3362‑6 *) | 850 | 3NE1448-2 |
1) Rated power based on the rated output current Irated. 2) Suitable for 3KL/3KD switch disconnector. *) 2 units **) 3 units Note: Important! Note the minimum short-circuit current required to trip the protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.
|