Recommended line-side power components Selection and ordering data The table below lists recommended ratings for input-end switching and fuse protection elements for compliance with IEC standards.
Notes for use in compliance with IEC standards:
3NA3 or 3NE1 fuses are recommended for European countries.
Notes for use in compliance with UL regulations:
UL-approved fuses must be used in North America.
Examples of fuses:Class J and class L fuses, supplied by Cooper Bussmann Additional information about the listed fuses can be found in Catalogs LV 10, IC 10 and IC 10 AO.
Rated power 1)
SINAMICS G120 PM330 Power Modules
Main contactor acc. to IEC
Switch disconnector acc. to IEC
Cable protection fuse incl. Solid-state contactor2)
IEC-compliant
Cable protection fuse acc. to IEC
Cable protection fuse
acc. to UL/cUL, Class J/L
400 V/690 V
460 V/575 V
Type
Rated current
Rated current
Minimum short-circuit current
Rated current
Minimum short-circuit current
Rated current
kW
hp
6SL3310-...
Frame size
Type
A
Type
A
A
Article No.
A
A
Article No.
A
Reference No. 3) or Article No.
380 ... 480 V 3 AC
160
200
1PE33-0AA0
GX
3RT1456 (2 units)
400
3KL5730
450
4400
3NE1333-2
400
9500
3NA3260
400
DFJ-400 Class J
200
250
1PE33-7AA0
GX
3RT1456 (2 units)
400
3KL5730
500
5200
3NE1334-2
500
14000
3NA3365
500
DFJ-500 Class J
250
300
1PE34-6AA0
GX
3RT1456 (3 units)
630
3KL6130
560
7000
3NE1435-2
630
20000
3NA3372
600
DFJ-600 Class J
315
400
1PE35-8AA0
HX
3RT1456 (3 units)
630
3KL6130
710
10000
3NE1437-2
650
KTU650 Class L
355
450
1PE36-6AA0
HX
3RT1466 (2 units)
800
3KL6230
800
11000
3NE1438-2
800
30000
3NA3475
700
KTU700 Class L
400
500
1PE37-4AA0
HX
3RT1466 (3 units)
800
3KL6230
850
13000
3NE1448-2
800
KTU800 Class L
450
500
1PE38-4AA0
JX
3RT1466 (3 units)
1000
3KD5034
2 ? 500
10400
3NE1334-3
(2 units)
1000
40000
3NA3480
1000
3NB3350-1KK26
500
600
1PE38-8AA0
JX
3RT1466 (3 units)
1000
3KD5034
2 ? 560
14000
3NE1435-3
(2 units)
1000
40000
3NA3480
1100
3NB3351-1KK26
560
700
1PE41-0AA0
JX
3RT1476 (2 units)
1250
3KD5234
2 ? 630
16000
3NE1436-3
(2 units)
1250
52000
3NA3482
1250
3NB3352-1KK26
500 ... 690 V 3 AC
500
500
1PG35-8AA0
JX
3RT1466 (3 units)
630
3KD4634
710
10000
3NE1437-2
2 x 355
16000
3NA3354-6
710
3NE1437-2
560 (751)
600
1PG36-5AA0
JX
3RT1466 (3 units)
800
3KD4834
800
11000
3NE1438-2
2 x 400
20000
3NA3360-6
800
3NE1438-2
630
700
1PG37-2AA0
JX
3RT1466 (3 units)
1000
3KD5034
850
13000
3NE1448-2
2 x 425
21000
3NA3362-6
850
3NE1448-2
1) Rated power based on the rated output current I rated .
2) Suitable for 3KL/3KD switch disconnector.
3) Recommendation: Class J or class L fuse supplied by Cooper Bussmann.
Note:
Important! Note the minimum short-circuit current required to trip the protection devices. If the minimum short circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.