Supply voltage | |
Load voltage L+ | |
| 24 V |
| Yes |
Input current | |
from load voltage L+ (without load), max. | 350 mA |
from backplane bus 5 V DC, max. | 110 mA |
Power loss | |
Power loss, typ. | 6 W |
Analog outputs | |
Number of analog outputs | 8 |
Current output, no-load voltage, max. | 24 V |
Output ranges, current | |
| Yes |
| No |
| Yes |
Connection of actuators | |
| Yes |
Load impedance (in rated range of output) | |
| 750 Ω |
| 10 mH |
Destruction limits against externally applied voltages and currents | |
| +60/-0.5 V |
Cable length | |
| 800 m |
Analog value generation for the outputs | |
Integration and conversion time/resolution per channel | |
| 16 bit |
Settling time | |
| 0.1 ms |
| 0.5 ms |
Errors/accuracies | |
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % |
Linearity error (relative to output range), (+/-) | 0.01 % |
Temperature error (relative to output range), (+/-) | 0.002 %/K |
Crosstalk between the outputs, min. | 70 dB |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % |
Operational error limit in overall temperature range | |
| 0.2 % |
Basic error limit (operational limit at 25 °C) | |
| 0.1 % |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information | |
Diagnostic functions | Yes |
Substitute values connectable | Yes |
Alarms | |
| Yes |
Diagnostic messages | |
| Yes |
Diagnostics indication LED | |
| Yes |
Potential separation | |
Potential separation analog outputs | |
| No |
| Yes |
| Yes |
Isolation | |
Isolation tested with | 500 V DC |
Degree and class of protection | |
IP degree of protection | IP20 |
Connection method | |
required front connector | 20-pin |
Dimensions | |
Width | 40 mm |
Height | 125 mm |
Depth | 117 mm |
Weights | |
Weight, approx. | 220 g |