Supply voltage | | |
Rated value (DC) | 24 V; 1L+ | 24 V; 1L+ |
Reverse polarity protection | Yes | Yes |
Load voltage L+ | | |
| 24 V; 2L+, 3L+ | 24 V; 2L+, 3L+ |
| No | No |
Input current | | |
from supply voltage 1L+, max. | 100 mA | 75 mA |
from load voltage 2L+ (without load), max. | 100 mA | 100 mA |
from load voltage 3L+ (without load), max. | 100 mA | 100 mA |
from backplane bus 5 V DC, max. | 100 mA | 100 mA |
Power loss | | |
Power loss, typ. | 6 W | 12 W |
Digital outputs | | |
Number of digital outputs | 10 | 8 |
Short-circuit protection | Yes | Yes |
Limitation of inductive shutdown voltage to | | L+ (-33 V) |
Switching capacity of the outputs | | |
| 5 W | 5 W |
Output voltage | | |
| L+ (-1.0 V) | L+ (-1.0 V) |
Output current | | |
| 2 A | 2 A |
| 7 mA | 7 mA |
| 2.4 A | 2 A; 2 A for horizontal installation, 1 A for vertical installation |
| 7 mA | 7 mA |
| 2.4 A | 1 A; for horizontal installation |
| 0.5 mA | 0.5 mA |
Switching frequency | | |
| 25 Hz | 30 Hz |
| 25 Hz | 2 Hz |
| 10 Hz | 10 Hz |
Total current of the outputs (per group) | | |
horizontal installation | | |
| 10 A | 7.5 A |
| 6 A | 5 A |
vertical installation | | |
| 5 A | 5 A |
Cable length | | |
| 1 000 m | 200 m; 200 m for SIL3, AK 6, Cat 4 |
| 600 m | 200 m |
Interrupts/diagnostics/status information | | |
Alarms | | |
| Yes | Yes; Parameterizable |
Diagnostic messages | | |
| Yes | Yes |
Diagnostics indication LED | | |
| Yes | Yes |
| Yes | Yes |
Potential separation | | |
Potential separation digital outputs | | |
| Yes | Yes |
| 5 | 4 |
| Yes | Yes |
| Yes | Yes |
Isolation | | |
Isolation tested with | 370V for 1 min | 500 V DC/350 V AC |
Highest safety class achievable in safety mode | | |
| AK 5 and 6 | |
| Cat. 4 | Cat. 4 |
| SIL 3 | SIL 3 |
Connection method | | |
required front connector | 40-pin | 40-pin |
Dimensions | | |
Width | 40 mm | 80 mm |
Height | 125 mm | 125 mm |
Depth | 120 mm | 120 mm |
Weights | | |
Weight, approx. | 330 g | 465 g |