Supply voltage | |
Load voltage L+ | |
| 24 V |
| Yes |
Input current | |
from load voltage L+ (without load), max. | 50 mA |
from backplane bus 5 V DC, max. | 80 mA |
Encoder supply | |
Type of output voltage | via the inputs |
Power loss | |
Power loss, typ. | 1.1 W |
Digital inputs | |
Number of NAMUR inputs | 4 |
Input voltage | |
| 8.2 V; from internal power circuit supply |
Input current | |
| 0.1 mA |
| 8.5 mA |
for NAMUR encoders | |
| 0.35 to 1.2 mA |
| 2.1 to 7 mA |
Input delay (for rated value of input voltage) | |
| 2 kHz |
for NAMUR inputs | |
| Yes; 0.1 / 0.5 / 3 / 15 / 20 ms (plus 0.25 ms preparation time) |
Cable length | |
| 200 m |
Encoder | |
Connectable encoders | |
| Yes; Two-wire connection |
Interrupts/diagnostics/status information | |
Diagnostic functions | Yes |
Diagnostic messages | |
| Yes |
Diagnostics indication LED | |
| Yes |
| Yes |
| Yes |
Ex(i) characteristics | |
Module for Ex(i) protection | Yes |
Maximum values of input circuits (per channel) | |
| 3 µF |
| 14.1 mA |
| 100 mH |
| 33.7 mW |
| 10 V |
Potential separation | |
Potential separation digital inputs | |
| Yes |
| 1 |
Standards, approvals, certificates | |
Use in hazardous areas | |
| [EEx ib] IIC |
| Class II, Division 2, Group A, B, C, D T4 |
| Ex-96.D.2094X |
Ambient conditions | |
Ambient temperature during operation | |
| 60 °C |
Connection method | |
required front connector | 20-pin |
Weights | |
Weight, approx. | 230 g |