General information | |
Product type designation | F-DI 16x24VDC |
Product function | |
| Yes; I&M0 to I&M3 |
Engineering with | |
| V13 SP1 with HSP0086 |
Operating mode | |
| Yes |
Supply voltage | |
Type of supply voltage | 24 V DC |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Encoder supply | |
Number of outputs | 4 |
Short-circuit protection | Yes; Electronic (response threshold 0.7 A to 1.8 A) |
24 V encoder supply | |
| Yes; min. L+ (-1.5 V) |
| Yes |
| 300 mA; Max. 100 mA when mounted vertically |
Digital inputs | |
Number of digital inputs | 16 |
Source/sink input | Yes; P-reading |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Input voltage | |
| DC |
| 24 V |
| -30 to +5V |
| +15 to +30V |
Input current | |
| 3.7 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
| Yes |
Cable length | |
| 1 000 m |
| 500 m |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Alarms | |
| Yes |
| No |
Diagnostic messages | |
| Yes |
| No |
| Yes |
| Yes |
Diagnostics indication LED | |
| Yes; Green LED |
| Yes; Red LED |
| Yes; Green LED |
| Yes; Red LED |
| Yes; Red LED |
Potential separation | |
Potential separation channels | |
| Yes |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Standards, approvals, certificates | |
Suitable for safety functions | Yes |
Highest safety class achievable in safety mode | |
| PLe |
| SIL 3 |
Probability of failure (for service life of 20 years and repair time of 100 hours) | |
| < 5.00E-05 |
| < 1.00E-09 1/h |
Ambient conditions | |
Ambient temperature during operation | |
| 0 °C |
| 60 °C |
| 0 °C |
| 40 °C |
Dimensions | |
Width | 35 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 280 g |