FOUNDATION Fieldbus H1 | |
Data transmission | MBP |
Transmission rate | 31.25 Kbps |
Cable | 2-wire shielded |
Topology | Line, tree, ring |
FF devices per segment/FF Link | 31 |
Active field distributors per segment/FF Link | |
| 8 |
- AFDiSD or combinations of AFDiSD and AFD
| 5 |
Max. total current consumption of all FF field devices | 0.5 A |
Cable length per segment | 1 900 m |
Bus segments with AFD | |
Max. spur line length related to the total number of spur lines Number of spur lines (1 device per spur line) | |
| 120 m |
| 90 m |
| 60 m |
| 30 m |
| 1 m |
Bus segments with AFDiSD | |
Max. spur line length independent of total number of spur lines Number of spur lines (1 device per spur line) | |
| |
| 120 m |
- Intrinsically-safe acc. to FISCO
| 120 m |