Supply voltage | |
Load voltage L+ | |
| 24 V |
Input current | |
from load voltage L+ (without load), max. | 200 mA |
from backplane bus 5 V DC, max. | 80 mA |
Power loss | |
Power loss, typ. | 4 W |
Analog outputs | |
Number of analog outputs | 4 |
Voltage output, short-circuit protection | Yes |
Voltage output, short-circuit current, max. | 70 mA |
Current output, no-load voltage, max. | 14 V |
Output ranges, current | |
| Yes |
| Yes |
Connection of actuators | |
| Yes |
Load impedance (in rated range of output) | |
| 500 ? |
Cable length | |
| 200 m |
Analog value generation for the outputs | |
Integration and conversion time/resolution per channel | |
| 15 bit |
| 2.5 ms |
Errors/accuracies | |
Operational error limit in overall temperature range | |
| 0.55 % |
Basic error limit (operational limit at 25 °C) | |
| 0.2 % |
Interrupts/diagnostics/status information | |
Diagnostic messages | |
| Yes |
| Yes |
| Yes |
Ex(i) characteristics | |
Maximum values of output circuits (per channel) | |
| 850 nF |
| 70 mA |
| 6.6 mH |
| 440 mW |
| 14 V |
Potential separation | |
Potential separation analog outputs | |
| Yes |
Permissible potential difference | |
between the outputs (UCM) | 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
Between the outputs and MANA (UCM) | 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
Standards, approvals, certificates | |
Use in hazardous areas | |
| [EEx ib] IIC |
| Class I, Division 2, Group A, B, C, D T4 |
| Ex-96.D.2026X |
Ambient conditions | |
Ambient temperature during operation | |
| 60 °C |
Connection method | |
required front connector | 20-pin |
Weights | |
Weight, approx. | 280 g |