Supply voltage | | |
Load voltage L+ | | |
| 24 V | 24 V |
Input current | | |
from load voltage L+ (without load), max. | 160 mA | 160 mA |
from backplane bus 5 V DC, max. | 85 mA | 85 mA |
Power loss | | |
Power loss, typ. | 3 W | 3 W |
Digital outputs | | |
Number of digital outputs | 4 | 4 |
Short-circuit protection | Yes; Electronic | Yes; Electronic |
| Output current with short-circuit protection, min. 10 mA + 10 % | Output current with short-circuit protection, min. 20.5 mA + 10 % |
Load resistance range | | |
| 390 ?; Two-wire connection | 200 ?; Two-wire connection |
Output voltage | | |
| 24 V | 15 V |
Output current | | |
| 10 mA; +/-10 % | 20 mA; +/-10 % |
Switching frequency | | |
| 100 Hz | 100 Hz |
Cable length | | |
| 200 m | 200 m |
Interrupts/diagnostics/status information | | |
Diagnostic messages | | |
| Yes | Yes |
| Yes | Yes |
Ex(i) characteristics | | |
Maximum values of output circuits (per channel) | | |
| 90 nF | 500 nF |
| 70 mA | 85 mA |
| 6.7 mH | 5 mH |
| 440 mW | 335 mW |
| 25.2 V | 15.75 V |
Potential separation | | |
Potential separation digital outputs | | |
| Yes | Yes |
| 1 | 1 |
Standards, approvals, certificates | | |
Use in hazardous areas | | |
| [EEx ib] IIC | [EEx ib] IIC |
| Class I, Division 2, Group A, B, C, D T4 | AIS CL.1, DIV 1, GP A, B, C, D; CL.I, DIV 2, GP A, B, C, D T4 |
| Ex-96.D.2093X | Ex-96.D.2102X |
Ambient conditions | | |
Ambient temperature during operation | | |
| 60 °C | 60 °C |
Connection method | | |
required front connector | 20-pin | 20-pin |
Weights | | |
Weight, approx. | 230 g | 230 g |