General information | |
Product type designation | F-DQ 8x24VDC/2A PPM |
Firmware version | |
| Yes |
Product function | |
| Yes; I&M0 to I&M3 |
Operating mode | |
| Yes |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current | |
Current consumption (rated value) | 110 mA; without load |
Output voltage | |
Rated value (DC) | 24 V |
Power | |
Power available from the backplane bus | 0.8 W |
Power loss | |
Power loss, typ. | 11 W |
Address area | |
Address space per module | |
| 6 byte |
Hardware configuration | |
Automatic encoding | Yes |
| Yes |
Digital outputs | |
Number of digital outputs | 8 |
Current-sinking | Yes |
Current-sourcing | Yes |
Short-circuit protection | Yes |
Open-circuit detection | Yes |
| 8 mA |
Overload protection | Yes |
| 2.9 A |
Limitation of inductive shutdown voltage to | PM-switching: -24 V + (-47 V), PP-switching: -24 V |
Switching capacity of the outputs | |
| 2 A |
| 10 W |
Load resistance range | |
| 12 Ω |
| 2 000 Ω |
Output voltage | |
| 24 V; L+ (-0.5 V) |
Output current | |
| 2 A |
| 0.5 mA; Current-sourcing, or current sourcing and sinking switches individually, current sinking: max. 1 mA |
Switching frequency | |
| 30 Hz |
| 0.1 Hz |
| 10 Hz |
Total current of the outputs | |
| 2 A |
Total current of the outputs (per module) | |
horizontal installation | |
| 16 A |
| 8 A |
vertical installation | |
| 8 A |
Cable length | |
| 1 000 m |
| 500 m |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Substitute values connectable | No |
Alarms | |
| Yes |
Diagnostic messages | |
| Yes |
| Yes |
| Yes |
| Yes |
Diagnostics indication LED | |
| Yes; Green LED |
| Yes; Red LED |
| Yes |
| Yes; Green LED |
| Yes; Red LED |
| Yes; Red LED |
Potential separation | |
Potential separation channels | |
| No |
| Yes |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 60 °C; = Tmax |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | |
Width | 35 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 300 g |