Supply voltage | |
Rated value (DC) | |
| Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current | |
from backplane bus 5 V DC, max. | 155 mA; Current consumption (SM Bus, 5 V DC): 155 mA |
Digital inputs | |
| 130 mA; 130 mA + 6 mA / input used + any Vs1/Vs2 current used |
Power loss | |
Power loss, typ. | 7 W |
Digital inputs | |
Number of digital inputs | 16; 16 (1oo1) or 8 (1oo2); Note: You can individually assign each pair of inputs "a.x" and "b.x" as a single (1oo2)-channel or as 2 separate (1oo1)-channels |
horizontal installation | |
| 16; 16 inputs at 55 °C horizontal |
vertical installation | |
| 16; 16 inputs at 45 °C vertical |
Input voltage | |
| -30 V DC to +5 V DC |
| 15 V DC to 30 V DC |
Input current | |
| 0.5 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
| Yes; 0.8 / 1.6 / 3.2 / 6.4 / 12.8 ms |
Cable length | |
| 200 m; Unshielded with input filter time of 1.6 ms to 12.6 ms (With an input delay of 0.8 ms, shielded cables must be used for the digital inputs and the sensor supply) |
| 200 m; Shielded with input filter time of 0.8 ms to 12.6 s (With an input delay of 0.8 ms, shielded cables must be used for the digital inputs and the sensor supply) |
Diagnostics indication LED | |
| Yes |
Standards, approvals, certificates | |
CE mark | Yes |
cULus | Yes |
FM approval | No |
Highest safety class achievable in safety mode | |
| 1-channel, Category 3, PL d; 2-channel, Category 3 or 4, PL e |
| SIL 2 (single-channel), SIL 3 (two-channel) |
Ambient conditions | |
Free fall | |
| 0.3 m; five times, in product package |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 55 °C; = Tmax |
| 5°C to 55°C, 3°C / minute |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Mechanics/material | |
Enclosure material (front) | |
| Yes |
Dimensions | |
Width | 70 mm |
Height | 100 mm |
Depth | 75 mm |
Weights | |
Weight, approx. | 250 g |