General information | | | | | | |
Product type designation | Type K0 | Type H1 | Type M1 | Type K0 | Type H1 | Type M1 |
Product function | | | | | | |
| Yes; Asset data | Yes; Asset data | Yes; Asset data | Yes; Asset data | Yes; Asset data | Yes; Asset data |
Supply voltage | | | | | | |
Rated value (DC) | 24 V | 24 V | 24 V | 24 V | 24 V | 24 V |
external protection for power supply lines | Yes; 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic | Yes; 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic | Yes; 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic | | | |
Current carrying capacity | | | | | | |
up to 70 °C, max. | 10 A | 10 A | 10 A | 10 A | 10 A | 10 A |
For process terminals, max. | 5 A | 2 A | 2 A | 5 A | 2 A | 2 A |
Hardware configuration | | | | | | |
Temperature sensor | | Yes; For internal reference junction with connecting thermocouple | Yes; For internal reference junction with connecting thermocouple | | Yes; For internal reference junction with connecting thermocouple | Yes; For internal reference junction with connecting thermocouple |
Formation of potential groups | | | | | | |
| Yes | Yes | Yes | No | No | No |
| No | No | No | Yes | Yes | Yes |
Analog inputs | | | | | | |
Thermocouple (TC) | | | | | | |
Temperature compensation | | | | | | |
| | Yes | Yes | | Yes | Yes |
Potential separation | | | | | | |
between backplane bus and supply voltage | Yes; 4 200 V DC/1 min, type test (due to half the isolating distance (basic isolation) for ГњK-III requirement of F technology) | Yes; 4 200 V DC/1 min, type test (due to half the isolating distance (basic isolation) for ГњK-III requirement of F technology) | Yes; 4 200 V DC/1 min, type test (due to half the isolating distance (basic isolation) for ГњK-III requirement of F technology) | Yes; 4 200 V DC/1 min, type test (due to half the isolating distance (basic isolation) for ГњK-III requirement of F technology) | Yes; 4 200 V DC/1 min, type test (due to half the isolating distance (basic isolation) for ГњK-III requirement of F technology) | Yes; 4 200 V DC/1 min, type test (due to half the isolating distance (basic isolation) for ГњK-III requirement of F technology) |
between the potential groups | Yes; 1 500 V DC/1 min, type test (SELV / PELV to functional ground FE) | Yes; 1 500 V DC/1 min, type test (to functional ground FE) | Yes; 1 500 V DC/1 min, type test (to functional ground FE) | Yes; 1 500 V DC/1 min, type test (SELV / PELV to functional ground FE) | Yes; 1 500 V DC/1 min, type test (to functional ground FE) | Yes; 1 500 V DC/1 min, type test (to functional ground FE) |
between process terminals and supply voltage | Yes; 4 200 V DC/1 min, type test (safe separation also exists between the 4 groups within the process terminals; furthermore, a safe separation 120 V AC to 120 V AC between all process terminals exists, with a test voltage of 3 800 V DC/1 min, type test) | Yes; 1 500 V DC/1 min, type test | Yes; 1 500 V DC/1 min, type test | Yes; 4 200 V DC/1 min, type test (safe separation also exists between the 4 groups within the process terminals; furthermore, a safe separation 120 V AC to 120 V AC between all process terminals exists, with a test voltage of 3 800 V DC/1 min, type test) | Yes; 1 500 V DC/1 min, type test | Yes; 1 500 V DC/1 min, type test |
Ambient conditions | | | | | | |
Ambient temperature during operation | | | | | | |
| -40 °C | -40 °C | -40 °C | -40 °C | -40 °C | -40 °C |
| 70 °C | 70 °C | 70 °C | 70 °C | 70 °C | 70 °C |
| -40 °C | -40 °C | -40 °C | -40 °C | -40 °C | -40 °C |
| 60 °C | 60 °C | 60 °C | 60 °C | 60 °C | 60 °C |
Dimensions | | | | | | |
Width | 22.5 mm | 22.5 mm | 45 mm | 22.5 mm | 22.5 mm | 45 mm |
Height | 175 mm | 175 mm | 175 mm | 175 mm | 175 mm | 175 mm |
Depth | 77 mm | 77 mm | 77 mm | 77 mm | 77 mm | 77 mm |
Weights | | | | | | |
Weight, approx. | 78 g | 80 g | 155 g | 78 g | 80 g | 155 g |