Line voltage 380 ... 480 V 3 AC | Active Interface Modules |
|---|
| 6SL3300-7TE32-6AA1 | 6SL3300-7TE33-8AA1 | 6SL3300-7TE35-0AA1 |
|---|
Suitable for Active Line Module | | | | | | | kW | 132 | 160 | 235 | 300 | | | 6SL3330-7TE32-1AA3 | 6SL3330-7TE32-6AA3 | 6SL3330-7TE33-8AA3 | 6SL3330-7TE35-0AA3 | | | – | – | – | 6SL3335-7TE35-0AA3 | Rated current | A | 210 | 260 | 380 | 490 | Bypass contactor | | Included | Included | Included | Included | Current demand | | | | | | - 24 V DC auxiliary power supply
| A | 0.17 | 0.17 | 0.17 | 0.17 | | | | | | | | A | 1.25 | 1.25 | 2.5 | 2.5 | | A | 0.6 | 0.6 | 1.2 | 1.2 | DC link capacitance of drive line-up, max. 1) | μF | 41600 | 41600 | 76800 | 76800 | Power loss, max. 2) | | | | | | | kW | 2.1 | 2.2 | 3.0 | 3.9 | | kW | 2.1 | 2.2 | 3.0 | 3.9 | Cooling air requirement | m3/s (ft3/s) | 0.24 (8.48) | 0.24 (8.48) | 0.47 (16.6) | 0.47 (16.6) | Line/load connection L1, L2, L3 / U2, V2, W2 | | Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M10 screw | Flat connector for M10 screw | - Conductor cross-section, max. (IEC)
| mm2 | 2 × 185 | 2 × 185 | 2 × 185 | 2 × 185 | PE/GND connection | | 2 × M10 nut | 2 × M10 nut | 2 × M10 nut | 2 × M10 nut | - Conductor cross-section, max. (IEC)
| mm2 | 2 × 185 | 2 × 185 | 2 × 185 | 2 × 185 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | mm (in) | 325 (12.8) | 325 (12.8) | 325 (12.8) | 325 (12.8) | | mm (in) | 1400 (55.1) | 1400 (55.1) | 1533 (60.4) | 1533 (60.4) | | mm (in) | 355 (14.0) | 355 (14.0) | 544 (21.4) | 544 (21.4) | Weight, approx. | kg (lb) | 135 (298) | 135 (298) | 190 (419) | 190 (419) | Frame size | | FI | FI | GI | GI | Minimum short-circuit current 3) | A | 6200 | 10500 | 10500 | 8000 |
1)Information on higher capacities is included in the SINAMICS Low Voltage Engineering Manual. 2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 3) Current required for reliable triggering of the protective devices. Line voltage 380 ... 480 V 3 AC | Active Interface Modules |
|---|
| 6SL3300-7TE38-4AA1 | 6SL3300-7TE41-4AA1 |
|---|
Suitable for Active Line Module | | | | | | | kW | 380 | 450/500 | 630 | 800/900 | | | 6SL3330-7TE36-1AA3 | 6SL3330-7TE37-5AA3 6SL3330-7TE38-4AA3 | 6SL3330-7TE41-0AA3 | 6SL3330-7TE41-2AA3 6SL3330-7TE41-4AA3 | Rated current | A | 605 | 745/840 | 985 | 1260/1405 | Bypass contactor | | 3RT1476-6AP36 | 3WL1110-2BB34-4AN2-Z C22 1) | 3WL1112-2BB34-4AN2-Z C22 1) | 3WL1116-2BB34-4AN2-Z C22 1) | Current demand | | | | | | - 24 V DC auxiliary power supply
| A | 0.17 | 0.17 | 0.17 | 0.17 | | | | | | | | A | 9.9 | 9.9 | 10.5 | 10.5 | | A | 4.6 | 4.6 | 4.9 | 4.9 | DC link capacitance of the drive line-up, max. 2) | μF | 134400 | 134400 | 230400 | 230400 | Power loss, max. 3) | | | | | | | kW | 5.5 | 6.1 | 7.5 | 8.5 | | kW | 5.5 | 6.1 | 7.5 | 8.5 | Cooling air requirement | m3/s (ft3/s) | 0.4 (14.1) | 0.4 (14.1) | 0.4 (14.1) | 0.4 (14.1) | Line/load connection L1, L2, L3 / U2, V2, W2 | | 4 × hole for M12 | 4 × hole for M12 | 3 × hole for M12 | 3 × hole for M12 | - Conductor cross-section, max. (IEC)
| mm2 | 4 × 240 | 4 × 240 | 6 × 240 | 6 × 240 | PE/GND connection | | 2 × M12 nut | 2 × M12 nut | 4 × M12 nut | 4 × M12 nut | - Conductor cross-section, max. (IEC)
| mm2 | 2 × 240 | 2 × 240 | 4 × 240 | 4 × 240 | Degree of protection | | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | mm (in) | 305 (12.0) | 305 (12.0) | 505 (19.9) | 505 (19.9) | | mm (in) | 1750 (68.9) | 1750 (68.9) | 1750 (68.9) | 1750 (68.9) | | mm (in) | 544 (21.4) | 544 (21.4) | 544 (21.4) | 544 (21.4) | Weight, approx. | kg (lb) | 390 (860) | 390 (860) | 480 (1058) | 480 (1058) | Frame size | | HI | HI | JI | JI | Minimum short-circuit current 4) | A | 9200 | 8800/10400 | 16000 | 21000 |
1) The breakers must always be switched ON and OFF by the sequence control. An interlocking set 3WL9111‑0BA21‑0AA0 as described in Catalog LV 10 should be provided for the bypass contactor to exclude the risk of unintentional manual operation. Manual operation bypasses the pre-charging circuit and can therefore destroy the Active Line Module. 2)Information on higher capacities is included in the SINAMICS Low Voltage Engineering Manual. 3) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 4) Current required for reliably triggering protective devices. Line voltage 500 ... 690 V 3 AC | Active Interface Modules |
|---|
| 6SL3300-7TG35-8AA1 | 6SL3300-7TG37-4AA1 | 6SL3300-7TG41-3AA1 |
|---|
Suitable for Active Line Module | | | | | | | kW | 630 | 800 | 1100 | 1400 | | | 6SL3330-7TG35-8AA3 | 6SL3330-7TG37-4AA3 | 6SL3330-7TG41-0AA3 | 6SL3330-7TG41-3AA3 | | | 6SL3335-7TG35-8AA3 | – | – | – | Rated current | A | 575 | 735 | 1025 | 1270 | Bypass contactor | | 3RT1476-6AP36 | 3RT1476-6AP36 (3 units) | 3WL1212-4BB34-4AN2-Z C22 1) | 3WL1216-4BB34-4AN2-Z C22 1) | Current demand | | | | | | - 24 V DC auxiliary power supply
| A | 0.17 | 0.17 | 0.17 | 0.17 | | | | | | | | A | 9.9 | 10.5 | 10.5 | 10.5 | | A | 4.6 | 4.9 | 4.9 | 4.9 | DC link capacitance of the drive line-up, max. 2) | μF | 59200 | 153600 | 153600 | 153600 | Power loss, max. 3) | | | | | | | kW | 6.8 | 9.0 | 9.2 | 9.6 | | kW | 6.8 | 9.0 | 9.2 | 9.6 | Cooling air requirement | m3/s (ft3/s) | 0.4 (14.1) | 0.4 (14.1) | 0.4 (14.1) | 0.4 (14.1) | Line/load connection L1, L2, L3 / U2, V2, W2 | | 4 × hole for M12 | 3 × hole for M12 | 3 × hole for M12 | 3 × hole for M12 | - Conductor cross-section, max. (IEC)
| mm2 | 4 × 240 | 6 × 240 | 6 × 240 | 6 × 240 | PE/GND connection | | 2 × M12 nut | 4 × M12 nut | 4 × M12 nut | 4 × M12 nut | - Conductor cross-section, max. (IEC)
| mm2 | 2 × 240 | 4 × 240 | 4 × 240 | 4 × 240 | Degree of protection | | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | mm (in) | 305 (12.0) | 505 (19.9) | 505 (19.9) | 505 (19.9) | | mm (in) | 1750 (68.9) | 1750 (68.9) | 1750 (68.9) | 1750 (68.9) | | mm (in) | 544 (21.4) | 544 (21.4) | 544 (21.4) | 544 (21.4) | Weight, approx. | kg (lb) | 390 (860) | 430 (948) | 530 (1168) | 530 (1168) | Frame size | | HI | JI | JI | JI | Minimum short-circuit current 4) | A | 8400 | 10500 | 16000 | 20000 |
1) The breakers must always be switched ON and OFF by the sequence control. An interlocking set 3WL9111‑0BA21‑0AA0 as described in Catalog LV 10 should be provided for the bypass contactor to exclude the risk of unintentional manual operation. Manual operation bypasses the pre-charging circuit and can therefore destroy the Active Line Module. 2) Information on higher capacities is included in the SINAMICS Low Voltage Engineering Manual. 3) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 4) Current required for reliably triggering protective devices.
|
|