Siemens
ÑÐÅÄÑÒÂÀ ÏÐÎÌÛØËÅÍÍÎÉ ÀÂÒÎÌÀÒÈÇÀÖÈÈ
îôèöèàëüíûé ïàðòíåð Ñèìåíñ
Êàòàëîã ÑÀ01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6AG2132-6BH00-4BA0

6AG2132-6BF00-4CA0

6AG2132-6BD20-4BA0

SIPLUS ET 200SP DQ 16X24VDC/0.5A TX RAIL

SIPLUS ET 200SP DQ 8X24VDC/0.5A TX RAIL

SIPLUS ET 200SP DQ 4X24VDC/2A ST TX RAIL

General information

 

 

 

Product type designation

DQ 16x24 VDC/0.5 A ST

DQ 8x24 VDC/0.5 A ST

DQ 4x24 V DC/2 A ST

Firmware version

  • â—� FW update possible

Yes

Yes

Yes

usable BaseUnits

BU type A0

BU type A0

BU type A0

Color code for module-specific color identification plate

CC00

CC02

CC02

Product function

 

 

 

  • â—� I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Operating mode

 

 

 

  • â—� DQ

Yes

Yes

Yes

  • â—� DQ with energy-saving function

No

No

No

  • â—� PWM

No

No

No

  • â—� Oversampling

No

No

No

  • â—� MSO

No

Yes

No

Redundancy

 

 

 

  • â—� Redundancy capability

Yes

Yes

Yes

Supply voltage

 

 

 

Rated value (DC)

24 V

24 V

24 V

permissible range, lower limit (DC)

19.2 V

19.2 V

19.2 V

permissible range, upper limit (DC)

28.8 V

28.8 V

28.8 V

Reverse polarity protection

Yes

Yes

Yes

Input current

 

 

 

Current consumption, max.

60 mA; without load

60 mA; without load

Output voltage

 

 

 

Rated value (DC)

24 V

24 V

24 V

Power loss

 

 

 

Power loss, typ.

1 W

1 W

1 W

Address area

 

 

 

Address space per module

 

 

 

  • â—� Address space per module, max.

2 byte

8 byte; 2 channels per submodule + QI information

1 byte; + 1 byte for QI information

Digital outputs

 

 

 

Type of digital output

Source output (PNP, current-sourcing)

Source output (PNP, current-sourcing)

Number of digital outputs

16; > +60 °C max. total current 1.0 A

8; > +60 °C max. total current 1.0 A

4; > +60 °C number of simultaneously controllable outputs max. 2 x 0.25 A or max. 4 x 0.125 A, max. total current 0.5 A

Current-sinking

No

No

No

Current-sourcing

Yes

Yes

Yes

Short-circuit protection

Yes

Yes

Yes

  • â—� Response threshold, typ.

0.7 to 1.3 A

0.7 to 1.3 A

2.8 to 5.2 A

Limitation of inductive shutdown voltage to

Typ. L+ (-50 V)

Typ. L+ (-50 V)

Typ. L+ (-50 V)

Controlling a digital input

Yes

Yes

Yes

Switching capacity of the outputs

 

 

 

  • â—� with resistive load, max.

0.5 A

0.5 A

2 A

  • â—� on lamp load, max.

5 W

5 W

10 W

Load resistance range

 

 

 

  • â—� lower limit

48 â„¦

48 â„¦

12 â„¦

  • â—� upper limit

12 kΩ

12 kΩ

3 400 â„¦

Output current

 

 

 

  • â—� for signal "1" rated value

0.5 A

0.5 A

2 A

  • â—� for signal "0" residual current, max.

0.1 mA

0.1 mA

0.1 mA

Output delay with resistive load

 

 

 

  • â—� "0" to "1", typ.

50 µs

50 µs

50 µs

  • â—� "0" to "1", max.

50 µs

  • â—� "1" to "0", typ.

100 µs

100 µs

100 µs

  • â—� "1" to "0", max.

100 µs

Parallel switching of two outputs

 

 

 

  • â—� for uprating

No

No

No

  • â—� for redundant control of a load

Yes

Yes

Yes

Switching frequency

 

 

 

  • â—� with resistive load, max.

100 Hz

100 Hz

100 Hz

  • â—� with inductive load, max.

2 Hz

2 Hz

2 Hz

  • â—� on lamp load, max.

10 Hz

10 Hz

10 Hz

Total current of the outputs

 

 

 

  • â—� Current per channel, max.

0.5 A

0.5 A

2 A

  • â—� Current per module, max.

8 A

4 A

8 A

Total current of the outputs (per module)

 

 

 

horizontal installation

 

 

 

  • — up to 30 °C, max.

8 A

8 A

  • — up to 40 °C, max.

8 A

8 A

  • — up to 50 °C, max.

6 A

6 A

  • — up to 60 °C, max.

4 A

4 A

4 A

  • — up to 70 °C, max.

1 A

0.5 A

vertical installation

 

 

 

  • — up to 30 °C, max.

8 A

  • — up to 40 °C, max.

6 A

  • — up to 50 °C, max.

4 A; in all other mounting positions

4 A

  • — up to 60 °C, max.

4 A

Cable length

 

 

 

  • â—� shielded, max.

1 000 m

1 000 m

1 000 m

  • â—� unshielded, max.

600 m

600 m

600 m

Isochronous mode

 

 

 

Isochronous operation (application synchronized up to terminal)

No

Yes

No

Execution and activation time (TCO), min.

48 µs

Bus cycle time (TDP), min.

500 µs

Interrupts/diagnostics/status information

 

 

 

Diagnostics function

Yes

Yes

Yes

Substitute values connectable

Yes

Yes

Yes

Alarms

 

 

 

  • â—� Diagnostic alarm

Yes

Yes

Yes

Diagnostic messages

 

 

 

  • â—� Monitoring the supply voltage

Yes

Yes

Yes

  • â—� Wire-break

Yes; Module-wise

Yes; channel by channel

Yes; Module-wise

  • â—� Short-circuit

Yes; Module-wise

Yes; channel by channel

Yes; Module-wise

  • â—� Group error

Yes

Yes

Yes

Diagnostics indication LED

 

 

 

  • â—� Monitoring of the supply voltage (PWR-LED)

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

  • â—� Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • â—� for channel diagnostics

No

Yes; Red LED

No

  • â—� for module diagnostics

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Potential separation

 

 

 

Potential separation channels

 

 

 

  • â—� between the channels

No

No

No

  • â—� between the channels and backplane bus

Yes

Yes

Yes

Isolation

 

 

 

Isolation tested with

707 V DC (type test) and according to EN 50155 (routine test)

707 V DC (type test) and according to EN 50155 (routine test)

707 V DC (type test) and according to EN 50155 (routine test)

Standards, approvals, certificates

 

 

 

Railway application

 

 

 

  • â—� EN 50121-3-2

Yes; EMC for rail vehicles

Yes; EMC for rail vehicles

Yes; EMC for rail vehicles

  • â—� EN 50121-4

Yes; EMC for signal and telecommunications systems

Yes; EMC for signal and telecommunications systems

Yes; EMC for signal and telecommunications systems

  • â—� EN 50124-1

Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

  • â—� EN 50125-1

Yes; Rail vehicles - see ambient conditions

Yes; Rail vehicles - see ambient conditions

Yes; Rail vehicles - see ambient conditions

  • â—� EN 50125-2

Yes; Stationary electrical equipment - see ambient conditions

Yes; Stationary electrical equipment - see ambient conditions

Yes; Stationary electrical equipment - see ambient conditions

  • â—� EN 50125-3

Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

  • â—� EN 50155

Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2

Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2

Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2

  • â—� EN 61373

Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

  • â—� Fire protection acc. to EN 45545-2

Yes; Rail vehicles - verification on request

Yes; Rail vehicles - verification on request

Yes; Rail vehicles - verification on request

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • â—� horizontal installation, min.

-40 °C; = Tmin

-40 °C; = Tmin

-40 °C; = Tmin

  • â—� horizontal installation, max.

70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155)

70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155)

70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155)

Altitude during operation relating to sea level

 

 

 

  • â—� Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Relative humidity

 

 

 

  • â—� With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Use in stationary industrial systems

 

 

 

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Use on land craft, rail vehicles and special-purpose vehicles

 

 

 

  • — to biologically active substances according to EN 60721-3-5

Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request

Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request

Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request

  • — to chemically active substances according to EN 60721-3-5

Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-5

Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

Dimensions

 

 

 

Width

15 mm

15 mm

15 mm

Height

73 mm

73 mm

73 mm

Depth

58 mm

58 mm

58 mm

Weights

 

 

 

Weight, approx.

28 g

30 g

30 g

Other

 

 

 

Note:

For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776

For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776

For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776


















Êàòàëîã îáîðóäîâàíèÿ 2018
Siemens Industry Catalog Drive technology Automation technology Automation systems Operator control and monitoring systems SIMATIC HMI Identification systems Industrial communication Industrial controls Industry software PC-based Automation Process control systems Process instrumentation Process analytics SITOP power supply Products for specific requirements Automation technology for extreme conditions SIMATIC industrial automation systems Controllers SIPLUS IO systems SIPLUS ET 200 systems for the control cabinet ET 200SP SIPLUS interface modules SIPLUS extreme RAIL interface modules SIPLUS I/O modules SIPLUS digital inputs SIPLUS digital outputs SIPLUS analog inputs SIPLUS analog outputs SIPLUS technology modules SIPLUS communication SIPLUS failsafe I/O modules SIPLUS extreme RAIL digital inputs SIPLUS extreme RAIL digital outputs SIPLUS extreme RAIL analog inputs SIPLUS extreme RAIL analog outputs SIPLUS extreme RAIL technology modules SIPLUS extreme RAIL communication SIPLUS failsafe I/O modules SIPLUS BaseUnits SIPLUS BusAdapters SIPLUS extreme RAIL BaseUnits SIPLUS extreme RAIL BusAdapter ET 200S ET 200MP ET 200M SIPLUS PROFIBUS components for ET 200 SIPLUS extreme RAIL gateways SIMOTION Motion Control System Process control systems Operator control and monitoring systems Industrial communication Industrial controls Power supplies SIPLUS add-ons Telecontrol systems for comprehensive applications IO systems for heating elements Automatic door controllers Condition Monitoring Systems Time synchronization Energy Building Technologies Low-Voltage controls and distribution Safety Systems - Safety Integrated Market-specific solutions Industry Services Software ... and everything else you need




  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà