Input current | | |
from backplane bus 5 V DC, typ. | | 50 mA |
Output voltage | | |
Power supply to the transmitters | | |
| | 4 mA; per channel |
Power loss | | |
Power loss, typ. | 1 W | 1 W |
Digital inputs | | |
Number of digital inputs | 4 | 4 |
| | 1 |
Input characteristic curve in accordance with IEC 61131, type 2 | | Yes |
Number of simultaneously controllable inputs | | |
all mounting positions | | |
| | 4 |
Input voltage | | |
| DC | DC |
| | 24 V |
| | 0 to 5 V |
| | +15 to +30V |
Input current | | |
| | 2 mA |
| | 5.8 mA |
| | 14 mA |
Input delay (for rated value of input voltage) | | |
for standard inputs | | |
| | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
| | 2.5 µs |
for interrupt inputs | | |
| | Yes |
for counter/technological functions | | |
| | Yes |
Cable length | | |
| | 50 m; Standard input: 500 m, high-speed counters: 50 m |
Interrupts/diagnostics/status information | | |
Alarms | | Yes |
Diagnostic functions | | Yes |
Diagnostics indication LED | | |
| | Yes |
Degree and class of protection | | |
Degree of protection acc. to EN 60529 | | |
| | Yes |
Standards, approvals, certificates | | |
CE mark | | Yes |
Ambient temperature during operation | | |
| -40 °C; = Tmin; Startup @ -25 °C | -40 °C; = Tmin; Startup @ -25 °C |
| 60 °C; = Tmax; Tmax > 55 °C number of simultaneously activated inputs 2 (no adjacent points) for horizontal mounting position | 60 °C; = Tmax; Tmax > 55 °C number of simultaneously activated inputs 2 (no adjacent points) for horizontal mounting position |
Altitude during operation relating to sea level | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | |
| 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation |
Use in stationary industrial systems | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Mechanics/material | | |
Enclosure material (front) | | |
| | Yes |
Dimensions | | |
Width | 38 mm | 38 mm |
Height | 62 mm | 62 mm |
Depth | 21 mm | 21 mm |
Weights | | |
Weight, approx. | | 40 g |