Window-type current transformers | The conductor to be measured (busbar or cable) is passed through the window opening and creates the primary circuit of the window-type current transformer. |
Pin-wound transformers: An economical solution especially for small primary currents of 5 A to 75 A is achieved when the conductor to be measured is pin-wound several times. |
Primary rated operational current Ipn | Current transformers can be continuously loaded with 1.3 times the primary rated current (Ipn). |
Rated secondary current Isn | |
1 A | Particularly suitable for longer measuring leads. Cable losses of only 4 % in contrast to 5 A current transformers. |
5 A | 5 A current transformers create 25 times the power losses on measuring leads as compared with 1 A current transformers. These stray losses result in higher power in the case of long cables. Only recommended for use with short measuring leads. |
Accuracy class | |
Class 1 | Operation measurement, internal metering Current error ±1 % at 1 Г— Ipn and 1.2 Г— Ipn |
Class 3 | Coarse measurement Current error ±3 % at 0.5 Г— Ipn and 1.2 Г— Ipn |
Rated power Pn | The rated power of transformers is specified in VA. The actual load rating should be similar to the rated power; a lower actual load rating (underburden) increases the overcurrent factor and measuring instruments may be damaged in case of a short-circuit, a higher actual load rating (overburden) has a negative effect on the accuracy. |
With a frequency of 60 Hz the rated power increases to 1.2 times. With 162/3 Hz the output power decreases to 1/3 of the rated power. |
Maximum voltage for equipment Um | This is the rms value of the maximum voltage between the conductors of a network. For this voltage the insulation must be rated at normal operating conditions. |
4NC5 current transformers are suitable for 720 V. |
Overcurrent limiting factor FS | The overcurrent limiting factor is expressed using the characters FS and a factor, e.g. FS5 or FS10. |
When a short-circuit current flows through the primary winding of a current transformer, the load on the measuring instruments connected to the current transformer is the lower the smaller the overcurrent limiting factor is. |
Rated short-time thermal current Ith | The rated short-time thermal current Ith is the rms value of the primary current with a duration of one second, whose heat effect the current transformer can resist without being damaged in the event of a short-circuited secondary winding. |
Rated impulse current Idyn | The rated impulse current Idyn is the highest instantaneous value of the current after a short-circuit whose force the current transformer can resist without being damaged. |
The rated impulse current is specified as peak value. |