Supply voltage | | | | |
Rated value (DC) | | | | |
| Yes | Yes | Yes | Yes |
Input current | | | | |
Current consumption, typ. | 40mA | 40mA | 40mA | 40mA |
from backplane bus 5 V DC, typ. | 80mA | 80mA | 80mA | 80mA |
Power loss | | | | |
Power loss, typ. | 1.5W | 1.5W | 1.5W | 1.5W |
Analog inputs | | | | |
Number of analog inputs | 4; Resistance thermometer | 4; Resistance thermometer | 8; Resistance thermometer | 8; Resistance thermometer |
permissible input voltage for current input (destruction limit), max. | 35 V | 35 V | 35 V | 35 V |
Technical unit for temperature measurement adjustable | Degrees Celsius/degrees Fahrenheit | Degrees Celsius/degrees Fahrenheit | Degrees Celsius/degrees Fahrenheit | Degrees Celsius/degrees Fahrenheit |
Input ranges | | | | |
| Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000 | Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000 | Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000 | Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000 |
| Yes; 150 Ω, 300 Ω, 600 Ω | Yes; 150 Ω, 300 Ω, 600 Ω | Yes; 150 Ω, 300 Ω, 600 Ω | Yes; 150 Ω, 300 Ω, 600 Ω |
Input ranges (rated values), resistance thermometer | | | | |
| Yes | Yes | Yes | Yes |
| 10Ω | 10Ω | 10Ω | 10Ω |
| Yes | Yes | Yes | Yes |
| 100Ω | 100Ω | 100Ω | 100Ω |
| Yes | Yes | Yes | Yes |
| 1000Ω | 1000Ω | 1000Ω | 1000Ω |
| Yes | Yes | Yes | Yes |
| 1000Ω | 1000Ω | 1000Ω | 1000Ω |
| Yes | Yes | Yes | Yes |
| 120Ω | 120Ω | 120Ω | 120Ω |
| Yes | Yes | Yes | Yes |
| 200Ω | 200Ω | 200Ω | 200Ω |
| Yes | Yes | Yes | Yes |
| 500Ω | 500Ω | 500Ω | 500Ω |
| Yes | Yes | Yes | Yes |
| 100Ω | 100Ω | 100Ω | 100Ω |
| Yes | Yes | Yes | Yes |
| 1000Ω | 1000Ω | 1000Ω | 1000Ω |
| Yes | Yes | Yes | Yes |
| 200Ω | 200Ω | 200Ω | 200Ω |
| Yes | Yes | Yes | Yes |
| 500Ω | 500Ω | 500Ω | 500Ω |
Input ranges (rated values), resistors | | | | |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Thermocouple (TC) | | | | |
Temperature compensation | | | | |
| No | No | No | No |
Analog value generation for the inputs | | | | |
Measurement principle | integrating | integrating | integrating | integrating |
Integration and conversion time/resolution per channel | | | | |
| 15bit; + sign | 15bit; + sign | 15bit; + sign | 15bit; + sign |
| No | No | No | No |
| 85 dB at 50 / 60 / 400 Hz | 85 dB at 50 / 60 / 400 Hz | 85 dB at 50 / 60 / 400 Hz | 85 dB at 50 / 60 / 400 Hz |
Errors/accuracies | | | | |
Temperature error (relative to input range), (+/-) | 25 C 0.1%, to 55 C 0.2% total measurement range | 25 C 0.1% / 0.3% total measurement range | 25 C 0.1%, to 55 C 0.2% total measurement range | 25 C 0.1% / 0.3% total measurement range |
Repeat accuracy in steady state at 25 C (relative to output range), (+/-) | 0.05% | 0.05% | 0.05% | 0.05% |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | | | | |
| 120dB | 120dB | 120dB | 120dB |
Interrupts/diagnostics/status information | | | | |
Alarms | Yes | Yes | Yes | Yes |
Diagnostic functions | Yes; Can be read out | Yes; Can be read out | Yes; Can be read out | Yes; Can be read out |
Alarms | | | | |
| Yes | Yes | Yes | Yes |
Diagnostic messages | | | | |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Diagnostics indication LED | | | | |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Degree and class of protection | | | | |
Degree of protection acc. to EN 60529 | | | | |
| Yes | Yes | Yes | Yes |
Standards, approvals, certificates | | | | |
CE mark | Yes | Yes | Yes | Yes |
Ambient conditions | | | | |
Free fall | | | | |
| 0.3m; five times, in product package | 0.3m; five times, in product package | 0.3m; five times, in product package | 0.3m; five times, in product package |
Ambient temperature during operation | | | | |
| -20C; = Tmin; Startup @ 0 C | -40C; = Tmin; Startup @ -25 C | -20C; = Tmin; Startup @ 0 C | -40C; = Tmin; Startup @ -25 C |
| 60C; = Tmax | 70C; = Tmax | 60C; = Tmax | 70C; = Tmax |
Ambient temperature during storage/transportation | | | | |
| -40C | -40C | -40C | -40C |
| 70C | 70C | 70C | 70C |
Air pressure acc. to IEC 60068-2-13 | | | | |
| 660hPa | 660hPa | 660hPa | 660hPa |
| 1080hPa | 1080hPa | 1080hPa | 1080hPa |
Altitude during operation relating to sea level | | | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | | | |
| 95% | 95% | 95% | 95% |
| 100%; RH incl. condensation/frost (no commissioning under condensation conditions) | 100%; RH incl. condensation/frost (no commissioning under condensation conditions) | 100%; RH incl. condensation/frost (no commissioning under condensation conditions) | 100%; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | | | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method | | | | |
required front connector | Yes | Yes | Yes | Yes |
Mechanics/material | | | | |
Enclosure material (front) | | | | |
| Yes | Yes | Yes | Yes |
Dimensions | | | | |
Width | 45mm | 45mm | 70mm | 70mm |
Height | 100mm | 100mm | 100mm | 100mm |
Depth | 75mm | 75mm | 75mm | 75mm |
Weights | | | | |
Weight, approx. | 220g | 220g | 220g | 220g |