General information | |
Product type designation | IM 153-4 PN |
Vendor identification (VendorID) | 002AH |
Device identifier (DeviceID) | 0302H |
Supply voltage | |
Rated value (DC) | |
| Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
external protection for power supply lines (recommendation) | In a construction with grounded reference potential, a fuse is necessary for redundant interface modules (Recommendation: 2.5 A) |
Mains buffering | |
| 5 ms |
Input current | |
Current consumption, max. | 600 mA |
Inrush current, typ. | 4 A |
IІt | 0.09 AІ·s |
Output voltage | |
Rated value (DC) | 5 V |
Output current | |
for backplane bus (5 V DC), max. | 1.5 A |
Power loss | |
Power loss, typ. | 6 W |
Address area | |
Addressing volume | |
| 192 byte |
| 192 byte |
Hardware configuration | |
Number of modules per DP slave interface, max. | 12 |
Protocols | |
Bus protocol/transmission protocol | PROFINET IO |
Interrupts/diagnostics/status information | |
Diagnostics indication LED | |
| Yes |
| Yes |
Potential separation | |
Potential separation exists | Yes |
Isolation | |
Isolation tested with | 500 V DC |
Degree and class of protection | |
IP degree of protection | IP20 |
Standards, approvals, certificates | |
CE mark | Yes |
UL approval | Yes; File E239877 |
FM approval | Yes; CofC 3028431 |
RCM (formerly C-TICK) | Yes |
KC approval | Yes |
EAC (formerly Gost-R) | Yes |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | |
Width | 40 mm |
Height | 125 mm |
Depth | 118 mm |
Weights | |
Weight, approx. | 215 g; approx. |