Technology functionFunctions specific to pumps, fans and compressors are already integrated, e.g.: - Automatic restart
Application restart after a power failure or fault occurrence - Flying restart
Connection of the converter when the motor is running - Flux reduction
Automatic adaptation of the motor current to the prevailing load conditions in U/f control mode (ECO mode) as well as in sensorless vector control mode - Cascade connection
Load-dependent connection and disconnection of a maximum of three additional motors by the converter in order to provide a largely constant output power (implemented by means of an additional external circuit) - Hibernation mode
Startup or shutdown of the drive when the relevant value drops below an external setpoint or the internal PID controller setpoint - Real-time clock
For time-dependent process controls, e.g. to reduce the temperature of a heating control at night and with automatic daylight saving/standard time switchover - Freely programmable logical function blocks
For simulating simple PLC functions
Functions especially for building technology as well as heating/air conditioning/ventilation applications - 4 integrated PID controllers
One PID controller for controlling the drive speed as a function of pressure, temperature, flowrate, fill level, air quality and other process variables, and a further three PID controllers with freely configurable outputs, e.g. for controlling valves (heating, cooling) or flaps - Emergency mode
Special converter operating mode that enhances the availability of the drive system in the event of a fire Multi-zone controller- Closed-loop control of a zone with up to 3 sensors for pressure or temperature, or
- Closed-loop control of two independent zones, each with one sensor
- Bypass mode
When the setpoint is reached or a fault occurs, the system changes over to line operation (implemented by means of an additional external circuit) - Programmable time switches
|
|