Diaphragm seal, screwed gland with inside diaphragm |
Process connection | Nominal pressure |
- Male thread GЅB to EN 837-1
| PN 100, PN 250 |
- External thread Ѕ-14" NPT-M
| PN 100, PN 250 |
| |
| PN 10 ... PN 40 |
| Class 150, class 300 |
Sealing face for open measurement flange | |
- For stainless steel, mat. no. 1.4404/316L
| To EN 1092-1, form B1 or ASME B16.5 RF 125 ... 250 AA
|
Materials | |
- Lower section (in the case of process connection thread)
| Stainless steel, mat. no. 1.4404/316L |
| Stainless steel, mat. no. 1.4404/316L |
| | |
| | |
| | Monel 400, mat. no. 2.4360 |
| | Hastelloy C276, mat. no. 2.4819 |
| | Hastelloy C4, mat. no. 2.4602 |
| | Hastelloy C22, mat. no. 2.4602 |
| | Tantalum |
| | Titanium, mat. no. 3.7035 |
| | Nickel 201 |
| | Stainless steel 316L, gold plated, layer thickness approx. 25 µm |
- Top section (process connection in the case of an open measurement flange)
| Stainless steel, mat. no. 1.4404/316L |
| Stainless steel 1.4571/316Ti |
- Sealing material on the process connection
| Viton and/or (in the case of vacuum-free version) |
- Sealing material between top and bottom section
| Viton (FKM) (standard:) Teflon (PTFE) metal spring ring (silver-coated) |
Capillary | |
| Max. 10 m (32.8 ft) |
| 2 mm (0.079 inch) |
| 150 mm (5.9 inch) |
| Stainless steel protective tube, mat. no. 1.4301/304 |
Fill fluid | |
(for remote seals of sandwich and flange design) | |
| | |
| | |
| | - Halocarbon oil (for measuring O2)
|
| | |
Max. recommended process temperature | 170 °C (338 °F) |
Permissible ambient temperature | Dependent on the pressure transmitter and the fill fluid of the remote seal More information can be found in the technical specifications of the pressure transmitters and in the section "Technical specifications of fill fluid" in the technical description of the remote seals. |
Weight | Approx. 1.5 kg (3.3 lb) |
Certificates and approvals | |
Classification according to pressure equipment directive (PED 2014/68/EU) | For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 4, paragraph 3 (sound engineering practice) |