Supply voltage | |
Load voltage L+ | |
| 24 V |
| Yes |
Input current | |
from load voltage L+ (without load), max. | 350 mA |
from backplane bus 5 V DC, max. | 110 mA |
Power loss | |
Power loss, typ. | 6 W |
Analog outputs | |
Number of analog outputs | 8 |
Current output, no-load voltage, max. | 24 V |
Output ranges, current | |
| Yes |
| No |
| Yes |
Load impedance (in rated range of output) | |
| 750 Ω |
| 10 mH |
Cable length | |
| 800 m |
Analog value generation for the outputs | |
Integration and conversion time/resolution per channel | |
| 16 bit |
Settling time | |
| 0.1 ms |
| 0.5 ms |
Errors/accuracies | |
Operational error limit in overall temperature range | |
| 0.2 %; ±0.4 % @ < 0 °C or > 60 °C |
Basic error limit (operational limit at 25 °C) | |
| 0.1 % |
Interrupts/diagnostics/status information | |
Diagnostic functions | Yes |
Substitute values connectable | Yes |
Alarms | |
| Yes |
Diagnostic messages | |
| Yes |
Diagnostics indication LED | |
| Yes |
Potential separation | |
Potential separation analog outputs | |
| Yes |
Isolation | |
Isolation tested with | 500 V DC |
Standards, approvals, certificates | |
CE mark | Yes |
UL approval | Yes; File E239877 |
FM approval | Yes |
RCM (formerly C-TICK) | Yes |
KC approval | Yes |
EAC (formerly Gost-R) | Yes |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 60 °C; = Tmax |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method | |
required front connector | 20-pin |
Dimensions | |
Width | 40 mm |
Height | 125 mm |
Depth | 117 mm |
Weights | |
Weight, approx. | 220 g |