General information | |
Product type designation | IF 964-DP |
Input current | |
Current consumption, max. | 150 mA; Current consumption from S7-400 bus: The module uses no current at 24 V, it provides this voltage only at the DP interface. Total current consumption of the components connected to the DP interface, but maximum 150 mA. Current carrying capacity of the isolated 5 V (P5ext) maximum 90 mA, current carrying capacity of the 24 V maximum 150 mA. |
Power loss | |
Power loss, typ. | 1 W |
Interfaces | |
PROFIBUS DP | |
| 1 200 m; At 9.6 kbit/s: max. 1200 m; at 12 Mbit/s: max. 100 m |
1. Interface | |
Physics | RS 485 |
Isolated | Yes |
Functionality | |
| Yes; Default setting |
| Yes |
DP master | |
| 12 Mbit/s |
| 125; depending on the CPU used |
Services | |
| Yes |
| Yes |
| Yes |
| Yes |
Address area | |
| device-dependent |
| device-dependent |
User data per DP slave | |
| 244 byte |
| 244 byte |
Communication functions | |
Number of connections | |
| device-dependent |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 70 °C; = Tmax; @ 60°C for UL/ATEX/FM use |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state) |
Resistance | |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | |
Width | 26 mm |
Height | 54 mm |
Depth | 130 mm |
Weights | |
Weight, approx. | 65 g |