The following analog electronics modules can be used for connecting actuators/sensors in the context of SIMATIC PCS 7: Analog input modulesEM 4 AI U High Feature - 4 inputs for voltage measurements
- Input ranges:
- ± 10 V, resolution 15 bit + sign
- ± 5 V, resolution 15 bit + sign
- 0 to 10 V, resolution 15 bit
- 1 to 5 V, resolution 15 bit
- Electrically isolated from load voltage 2L+
- Diagnostics "Short-circuit of sensor supply to M" per module
- Diagnostics "Short-circuit, open-circuit" per channel (depending on measuring range)
- Hardware interrupt with limit violation on channel 0
- Permissible common mode voltage 5 V AC pp
EM 4 AI I High Feature - 4 inputs for current measurements
- Input ranges:
- ± 20 mA, resolution 15 bit + sign
- 0 to 20 mA, resolution 15 bit
- 4 to 20 mA, resolution 15 bit
- Two-wire and four-wire transmitters can be connected
- Electrically isolated from load voltage 2L+
- Diagnostics "Short-circuit of sensor supply to M" per module
- Diagnostics "Short-circuit, open-circuit" per channel (depending on measuring range)
- Hardware interrupt with limit violation on channel 0
- Permissible common mode voltage 5 V AC pp
EM 4 AI RTD High Feature - 4 inputs for isolated (floating) resistance measurements or
resistance thermometers with 2-, 3- and 4-wire connections - Input ranges:
- Resistance measurement: 150 О©; 300 О©; 600 О©; 3000 О©; resolution 15 bit
- Resistance thermometer: Pt100; Ni100; Ni120; Pt200; Ni200; Pt500; Ni500; Pt1000; Ni1000; resolution 15 bit + sign
- Automatic compensation of line resistances with 3-wire and 4-wire connections
- Parameterizable temperature coefficient with resistance-type sensors
- Electrically isolated from load voltage supply 1L+ and 2L+
- Linearization of sensor characteristics
- Diagnostics "Open-circuit" per channel (terminals 1 and 3 are monitored for open-circuit)
- Permissible common mode voltage 10 V AC pp
EM 4 AI TC High Feature - 4 inputs for isolated/non-isolated thermocouples or voltage measurement; resolution 15 bits + sign
- Input ranges:
- Voltage measurement ± 80 mV
- Thermocouples: Type B, E, J, K, L, N, R, S, T
- Inputs are isolated from the encoder voltage supply 1L+ and load voltage supply 2L+
- Linearization of the voltage characteristic (conversion of the thermoelectric voltage to a temperature value)
- Smoothing
- Interference frequency suppression
- Various options to compensate for the reference temperature
- Overflow and underflow diagnostics
Analog output modulesEM 4 AO U High Feature - 4 outputs for voltage output
- Output ranges:
- ± 10 V, resolution 15 bits + sign
- 1 to 5 V, resolution 14 bit
- 0 to 10 V, resolution 15 bit
- Electrically isolated from sensor supply voltage 1L+
- Diagnostics "Short-circuit of sensor supply to M" per module
- Diagnostics "Open-circuit in outputs" per channel
- Substitute value output
EM 4 AO I High Feature - 4 outputs for current output
- Output ranges:
- ± 20 mA, resolution 15 bit + sign
- 4 to 20 mA, resolution 14 bit
- 0 to 20 mA, resolution 15 bit
- Electrically isolated from sensor supply voltage 1L+
- Diagnostics "Short-circuit of sensor supply to M" per module
- Diagnostics "Open-circuit" per channel
- Substitute value output
|
|