General information | | |
Product version | V6 | V6 |
Input current | | |
Current consumption, max. | 220 mA | 240 mA |
Power loss | | |
Power loss, typ. | 0.77 W | 0.83 W |
Ambient conditions | | |
Ambient temperature during operation | | |
| -25 °C; = Tmin | -25 °C; = Tmin |
| 70 °C; = Tmax; @ 60°C for UL/ATEX/FM use | 70 °C; = Tmax; @ 60°C for UL/ATEX/FM use |
Altitude during operation relating to sea level | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | | |
Use in stationary industrial systems | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | | |
Width | 13 mm | 13 mm |
Height | 14 mm | 14 mm |
Depth | 58 mm | 58 mm |
Weights | | |
Weight, approx. | 14 g | 14 g |