Input current | |
from backplane bus 5 V DC, max. | 20 mA |
Power loss | |
Power loss, typ. | 6 W |
Digital inputs | |
Number of digital inputs | 32 |
Number of simultaneously controllable inputs | |
| 32 |
Input voltage | |
| DC |
| 24 V |
| -30 V DC to +5 V DC |
| 13 V DC to 30 V DC |
Input current | |
| 1.3 mA |
| 7 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
| 1.2 ms |
| 4.8 ms |
Cable length | |
| 1 000 m |
| 600 m |
Encoder | |
Connectable encoders | |
| Yes |
| 1.5 mA |
Interrupts/diagnostics/status information | |
Diagnostic functions | No |
Potential separation | |
Potential separation digital inputs | |
| 32 |
| Yes |
Isolation | |
Isolation tested with | 500 V DC |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 60 °C; = Tmax |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation |
Resistance | |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! |
Dimensions | |
Width | 25 mm |
Height | 290 mm |
Depth | 210 mm |
Weights | |
Weight, approx. | 500 g |