The CPU 414-5H features: - A powerful processor:
The CPU achieves command execution times as low as 18.75 ns per binary command. - 4 MB main memory (2 MB for programs, 2 MB for data);
load memory for user programs and configuration data for the S7-400 H automation system; fast main memory for runtime-relevant subroutines of the user program. - A memory card:
For expanding the integrated load memory. In addition to the program itself, the information contained in the load memory also includes configuration data for the S7-400H, which is why it takes up around twice as much space in the memory. The result is:- The integrated load memory is not sufficient for large programs, which is why a memory card is often required.
RAM and FEPROM cards are available (FEPROM for saving data even when power supply is disconnected).
- Flexible expansion options
Up to 131 072 digital and 81 932 analog inputs/outputs - MPI multi-point interface:
The MPI enables the creation of a simple network with up to 32 nodes and a data transfer rate of 187.5 kbit/s. The CPU can establish up to 64 connections to nodes on the communication bus (C bus) and the MPI. Note: If PROFIBUS DP and MPI interfaces are being used simultaneously, only the following bus connectors can be connected to the MPI interface:- With socket: 6ES7 972-0BB42-0XA0
- Without socket: 6ES7 972-0BA42-0XA0
- PROFIBUS DP interface:
The PROFIBUS DP interface allows a redundant, distributed automation configuration offering high speed and ease of use. From the user's point of view, the distributed I/O is handled like the centralized I/O (same configuring, addressing and programming). - PROFINET interface with 2 ports (switch):
Supports system redundancy and MRP (Media Redundancy Protocol) - Mode selector:
Toggle switch design. - Diagnostics buffer:
The last 120 alarm and interrupt events are stored in a ring buffer for diagnostic purposes. - Real-time clock:
Diagnostics reports from the CPU are provided with the date and time. - PROFIBUS DP interface:
The CPU 414-5H with PROFIBUS DP master interface enables distributed automation to be established at high speed and with easy operation. From the user's point of view, the distributed I/O is handled like the centralized I/O (same configuring, addressing and programming). Note: If PROFIBUS DP and MPI interfaces are being used simultaneously, only the following bus connectors can be connected to the MPI interface:- With socket: 6ES7 972-0BB42-0XA0
- Without socket: 6ES7 972-0BA42-0XA0
|
|