Supply voltage | |
Load voltage L+ | |
| 24 V |
| Yes |
Input current | |
from load voltage L+ (without load), max. | 20 mA |
from backplane bus 5 V DC, max. | 120 mA |
Output voltage | |
Power supply to the transmitters | |
| 24 V |
Power loss | |
Power loss, typ. | 1.5 W |
Analog inputs | |
Number of analog inputs | 8 |
permissible input current for current input (destruction limit), max. | 40 mA |
Input ranges | |
| No |
| Yes |
| No |
| No |
| No |
Input ranges (rated values), currents | |
| Yes |
| 240 Ω |
| 240 Ω |
| 240 Ω |
Cable length | |
| 800 m |
Analog value generation for the inputs | |
Measurement principle | Sigma Delta |
Integration and conversion time/resolution per channel | |
| 16 bit |
| Yes |
| 20 ms at 50 Hz; 16.6 ms at 60 Hz; 100 ms at 100 Hz |
| 10 / 50 / 60 Hz |
Encoder | |
Connection of signal encoders | |
| Yes |
| Yes |
Errors/accuracies | |
Operational error limit in overall temperature range | |
| 0.15 %; ±0.25 % @ < 0 °C or > 60 °C |
Basic error limit (operational limit at 25 °C) | |
| 0.1 % |
Interrupts/diagnostics/status information | |
Diagnostic functions | Yes |
Alarms | |
| Yes |
| Yes |
Diagnostic messages | |
| Yes |
Diagnostics indication LED | |
| Yes |
Potential separation | |
Potential separation analog inputs | |
| Yes |
Isolation | |
Isolation tested with | 500 |
Standards, approvals, certificates | |
CE mark | Yes |
UL approval | Yes; File E239877 |
FM approval | Yes; CofC 3028431 |
RCM (formerly C-TICK) | Yes |
KC approval | Yes |
EAC (formerly Gost-R) | Yes |
Railway application | |
| No |
| No |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 70 °C; = Tmax; 60 °C @ UL/cUL use |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method | |
required front connector | 20-pin |
Dimensions | |
Width | 40 mm |
Height | 125 mm |
Depth | 117 mm |
Weights | |
Weight, approx. | 205 g |