Module-specific specifications | |
Supported synchronous operation | no |
Number of outputs | 4 |
Cable length | |
| max. 600 m |
| max. 1000 m |
Parameter length | 1 byte |
Voltages, Currents, Potentials | |
Nominal load voltage L+ (from power module) | 24 … 48 V DC; 24 AC … 230 V |
- Polarity reversal protection
| no |
Total current of the outputs (per module) | max. 10 A |
Potential isolation | |
| no |
- Between the channels and backplane bus
| Yes |
Permissible potential difference | |
- Between the supply voltage and the backplane bus
| 75 V DC, 240 V AC |
Isolation tested | |
- Between the supply voltage and the backplane bus
| 500 V DC, 1500 V AC |
Diagnostic alarm | no |
Data for selecting an actuator | |
Short-circuit protection for the output | No, possible via PM-E or external |
Dimensions and weight | |
Dimensions W Г— H Г— D (mm, the total dimensions depend on the selected terminal module) | 15 x 81 x 52 |
Weight | Approx. 33 g |