Siemens
01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6AG1332-5HD01-7AB0

6AG1332-7ND02-4AB0

6AG1332-5HB01-2AB0

6AG1332-5HF00-2AB0

SIPLUS S7-300 SM332 4AA U/I

SIPLUS S7-300 SM332 4AA

SIPLUS S7-300 SM332 2AO

SIPLUS S7-300 SM 332 8AO - 40pol

Supply voltage

Load voltage L+

  • Rated value (DC)

24V

24V

24V; A power supply according to EN 50155 shall be used for railway applications

24V

  • Reverse polarity protection

Yes

Yes

Yes

Yes

Input current

from load voltage L+ (without load), max.

240mA

290mA

135mA

340mA

from backplane bus 5 V DC, max.

60mA

120mA

60mA

100mA

Power loss

Power loss, typ.

3W

3W

3W

6W

Analog outputs

Number of analog outputs

4

4; Isochronous mode

2

8; 4 @ +70 C

Voltage output, short-circuit protection

Yes

Yes

Yes

Yes

Voltage output, short-circuit current, max.

25mA

40mA

25mA

25mA

Current output, no-load voltage, max.

18V

18V

18V

18V

Output ranges, voltage

  • 0 to 10 V

Yes

Yes

Yes

Yes

  • 1 V to 5 V

Yes

Yes

Yes

Yes

  • -10 V to +10 V

Yes

Yes

Yes

Yes

Output ranges, current

  • 0 to 20 mA

Yes

Yes

Yes

Yes

  • -20 mA to +20 mA

Yes

Yes

Yes

Yes

  • 4 mA to 20 mA

Yes

Yes

Yes

Yes

Load impedance (in rated range of output)

  • with voltage outputs, min.

1kΩ

1kΩ

1kΩ

1kΩ

  • with voltage outputs, capacitive load, max.

1F

1F

1F

1F

  • with current outputs, max.

500Ω

500Ω

500Ω

500Ω

  • with current outputs, inductive load, max.

10mH

1mH

10mH

10mH

Cable length

  • shielded, max.

200m

200m

200m

200m

Analog value generation for the outputs

Integration and conversion time/resolution per channel

  • Resolution with overrange (bit including sign), max.

12bit; 10 V, 20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit

16bit

12bit; 10 V, 20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit

12bit; 10 V, 20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit

  • Conversion time (per channel)

0.8ms

200s; in isochronous mode 640 s

0.8ms

0.8ms

Settling time

  • for resistive load

0.2ms

0.2ms

0.2ms

0.2ms

  • for capacitive load

3.3ms

3.3ms

3.3ms

3.3ms

  • for inductive load

0.5ms; 0.5 ms (1 mH); 3.3 ms (10 mH)

0.5ms

0.5ms; 0.5 ms (1 mH); 3.3 ms (10 mH)

0.5ms; 0.5 ms (1 mH); 3.3 ms (10 mH)

Errors/accuracies

Operational error limit in overall temperature range

  • Voltage, relative to output range, (+/-)

0.5%; 0.6 % @ < 0 C or > 60 C

0.12%

0.5%; 0.6 % @ < 0 C or > 60 C

0.5%; 0.6 % @ < 0 C or > 60 C

  • Current, relative to output range, (+/-)

0.6%; 0.7 % @ < 0 C or > 60 C

0.18%

0.6%; /-0.7% @ < 0 C or > 60 C

0.6%; 0.7 % @ < 0 C or > 60 C

Basic error limit (operational limit at 25 C)

  • Voltage, relative to output range, (+/-)

0.4%

0.02%

0.4%

0.4%

  • Current, relative to output range, (+/-)

0.5%

0.02%

0.5%

0.5%

Interrupts/diagnostics/status information

Diagnostic functions

Yes; Parameterizable

Yes; Parameterizable

Yes; Parameterizable

Substitute values connectable

Yes; Parameterizable

Yes; Parameterizable

Yes; Parameterizable

Yes; Parameterizable

Alarms

  • Diagnostic alarm

Yes; Parameterizable

Yes

Yes; Parameterizable

Yes; Parameterizable

Diagnostic messages

  • Diagnostic information readable

Yes

Yes

Yes

Diagnostics indication LED

  • Group error SF (red)

Yes

Yes

Yes

Yes

Potential separation

Potential separation analog outputs

  • between the channels and backplane bus

Yes

Yes

Yes

Yes

Isolation

Isolation tested with

500 V DC

1500 V DC

500 V DC

500 V DC

Standards, approvals, certificates

CE mark

Yes

Yes

Yes

Yes

UL approval

Yes; File E239877

Yes; File E239877

Yes; File E239877

Yes; File E239877

FM approval

Yes; CofC 3028431

Yes

Yes; CofC 3028431

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

Yes

Yes

Yes

KC approval

Yes

Yes

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Yes

Yes

Railway application

  • EN 50121-4

No

No

No

  • EN 50155

No

Yes; T1 Category 1 Class A/B horizontal mounting position

No

Ambient conditions

Ambient temperature during operation

  • min.

-25C; = Tmin

0C; = Tmin

-25C; = Tmin

-25C

  • max.

70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use

60C; = Tmax

70C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 C (T1) or 60 C @ UL/ULhaz/ATEX/FM use applies

70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use

Ambient temperature during storage/transportation

  • min.

-40C

-40C

-40C

-40C

  • max.

70C

70C

70C

70C

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

Use in stationary industrial systems

  • to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

required front connector

20-pin

20-pin

20-pin

40-pin

Dimensions

Width

40mm

40mm

40mm

40mm

Height

125mm

125mm

125mm

125mm

Depth

120mm

120mm

120mm

120mm

Weights

Weight, approx.

220g

220g

220g

272g