The FM 355 and FM 355-2 modules have four separate control channels. The controllers have the following features: - Predefined controller structures for
- Fixed setpoint control
- Cascade controller
- Ratio control
- 3-component control
- Different operating modes
- Automatic mode
- Manual mode
- Safety mode
- Follow-up mode
- Backup mode
- Sampling time (depending on the resolution of the analog inputs and the compensation input):
- At 12 bits: 20 ms to 100 ms (FM 355‑2 only)
- At 14 bits: 100 ms to 500 ms (depending on the number of released analog inputs)
- 2 control algorithms:
- Self-optimizing temperature control algorithm
- PID algorithm
- Integrated online self-optimization without configuration (FM 355‑2 only)
- Faster adjustment to the operating point
- Convenient controller optimization
- Backup mode
The controller can continue to control independently in the event of CPU failure or CPU stop. To this end, configurable safety setpoints or safety manipulated variables are set. - Feed forward control
The analog inputs can optionally be used for feed forward control in addition to actual value recording.
|
|