Supply voltage | |
Load voltage L+ | |
| 24 V |
| Yes |
Input current | |
from supply voltage L+, max. | 400 mA |
from backplane bus 5 V DC, max. | 150 mA |
Power loss | |
Power loss, typ. | 9 W |
Analog outputs | |
Number of analog outputs | 8 |
Voltage output, short-circuit protection | Yes |
Voltage output, short-circuit current, max. | 30 mA |
Current output, no-load voltage, max. | 19 V |
Output ranges, voltage | |
| Yes |
| Yes |
| Yes |
Output ranges, current | |
| Yes |
| Yes |
| Yes |
Load impedance (in rated range of output) | |
| 1 kΩ |
| 1 µF |
| 500 Ω; 600 ohms if common-mode-voltage reduced to <1 V |
Cable length | |
| 200 m |
Analog value generation for the outputs | |
Integration and conversion time/resolution per channel | |
| 13 bit |
| 420 µs; 420 µs in the ranges 1 to 5 V and 4 to 20 mA; 300 µs in all ranges |
Settling time | |
| 0.1 ms |
| 3.5 ms |
| 0.5 ms |
Errors/accuracies | |
Operational error limit in overall temperature range | |
| 0.5 %; ±10 V, 0 to 10 V, 1 to 5 V |
| 1 %; ±20 mA, 4 to 20 mV |
Basic error limit (operational limit at 25 °C) | |
| 0.5 %; ±10 V, 0 to 10 V, 1 to 5 V |
| 0.5 %; ±20 mA, 0 to 20 mA |
Potential separation | |
Potential separation analog outputs | |
| Yes |
Isolation | |
Isolation tested with | 2 120 V DC between bus and L+/M; 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog section and L+/M; 2 120 V DC between analog section and local ground; 2 120 V DC between L+/M and local ground |
Dimensions | |
Width | 25 mm |
Height | 290 mm |
Depth | 210 mm |
Weights | |
Weight, approx. | 650 g |