Analog inputs AE1, AE2, AE3 and AE6 to AE11 (input module 6DR2800-8A) |
Input signal range | |
| 0/199.6 to 998 mV or 0/2 to 10 V |
| 0/4 to 20 mA |
Input impedance | |
| 200 kО© |
| 49.9 О© ± 0.1 % |
| > 500 kО© |
Common-mode voltage | 0 to 10 V |
Filter time constant | 50 ms |
Effect of temperature | |
| 0.05 %/10 K |
| 0.1 %/10 K |
Analog outputs AA1 to AA3 |
Rated signal range | 0 to 20 mA or 4 to 20 mA |
Operating range | 0 to 20.5 mA or 3.6 to 20.5 mA |
Load voltage | -1 to +18 V |
Max. inductive load | ≤ 0.1 H |
No-load voltage | ≤ 26 V |
Time constant | 300 ms |
Residual ripple 900 Hz | ≤ 0.2 % |
Resolution | ≤ 0.1 % |
Zero error | ≤ 0.3 % of measuring span |
Gain error | ≤ 0.3 % of measuring span |
Linearity error | ≤ 0.05 % of measuring span |
Load dependence | ≤ 0.1 % |
Effect of temperature | |
| ≤ 0.1 %/10 K |
| ≤ 0.1 %/10 K |
Transmitter supply L+ |
Rated voltage | 20 to 26 V |
On-load current | ≤ 100 mA, short-circuit proof |
Short-circuit current | ≤ 200 mA pulsed |
Digital inputs BE1 to BE4 |
Signal status "0" | ≤ 4.5 V or open |
Signal status "1" | ≥ 13 V |
Static destruction limit | ± 35 V |
Input impedance | ≥ 27 kΩ |
Digital outputs BA1 to BA8 (connected via wired-OR diodes) |
Signal status "0" | ≤ 1.5 V |
Signal status "1" | +19 to 26 V |
On-load current | < 50 mA |
Short-circuit current | < 80 mA pulsed |
Cycle time | > 60 ms, user program dependent |
A/D conversion |
Method | Successive approximation with > 120 measurements per input and averaging over 20 or 16.67 ms |
Resolution | 11 bit в‰Ў to 0.06 % |
Zero error | ≤ 0.2 % of the measuring span |
Gain error | ≤ 0.2 % of the measuring span |
Linearity error | ≤ 0.2 % of the measuring span |
Effect of temperature | |
| ≤ 0.05 %/10 K |
| ≤ 0.1 %/10 K |
Parameters |
Adjusting | with tA 2/3 (more – less) |
| Progressive |
Precision | |
| ≤ ± 0,5 ‰ throughout the complete temperature range |
| Absolute, depending on resolution |
Display technology |
Digital dd1, dd2 displays | 4Ѕ digit, 7-segment LEDs |
| Green |
| Red |
| 7 mm |
| Adjustable start and full scale |
| -1999 to 19999 |
| Adjustable |
| 1 to 100 cycles/display |
| 1 digit, but not better than A/D converter |
| Corresponding to A/D converter and analog inputs |
Digital dd3 display | 3-digit, 7-segment LEDs |
| Yellow |
| 7 mm |
| Adjustable start and full scale |
| -199 to 999 |
| Adjustable |
| 1 to 100 cycles/display, variable |
| 1 digit, but not better than A/D converter |
| Corresponding to A/D converter and analog inputs |
Analog dA1, dA2 displays | |
| Red |
| Green |
| LED array with 30 LEDs |
| -199.9 to 199.9 %, variable |
| < -0.85 % of display range; 1st LED flashes > 100.85 % of display range; 30th LED flashes |
| 1.7 % by alternate lighting of 1 or 2 LEDs, the center point of the illuminated LEDs acting as a pointer |
| Cyclic |