General information | |
Product type designation | SM 1226 F-DQ 2 x Relay |
Supply voltage | |
Rated value (DC) | |
| Yes |
Input current | |
from backplane bus 5 V DC, max. | 120 mA |
Digital outputs | |
| 300 mA |
Power loss | |
Power loss, typ. | 10 W |
Output voltage | |
| 5 V DC to 30 V DC |
| 5 V AC to 250 V AC |
Output current | |
| 5 A maximum per circuit and 10 A maximum of all circuits per module |
Relay outputs | |
| 2; 2 circuits per output |
Switching capacity of contacts | |
| 0.1 Hz, accordance with IEC 60947-5-1, DC-13; 2 Hz, accordance with IEC 60947-5-1, AC-15 |
| 2 Hz |
Cable length | |
| 200 m |
| 200 m |
Diagnostics indication LED | |
| Yes |
Standards, approvals, certificates | |
CE mark | Yes |
cULus | Yes |
FM approval | No |
Highest safety class achievable in safety mode | |
| SIL 3 |
Ambient conditions | |
Free fall | |
| 0.3 m; five times, in product package |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 55 °C; = Tmax |
Extended ambient conditions | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Mechanics/material | |
Enclosure material (front) | |
| Yes |
Dimensions | |
Width | 70 mm |
Height | 100 mm |
Depth | 75 mm |
Weights | |
Weight, approx. | 300 g |