Line voltages | 380 ... 480 V 3 AC, ±10 % (-15 % <1 min) 500 … 690 V 3 AC, ±10 % (-15 % <1 min) |
Line supply types | Grounded TN/TT systems and non-grounded IT systems |
Line frequency | 47 ... 63 Hz |
Output frequency 1) | |
| 0 ... 550 Hz |
| 0 ... 550 Hz |
| 0 ... 550 Hz |
Line power factor Fundamental | |
| >0.96 |
| >0.96 |
| Adjustable (factory-set to cos ? = 1) |
Efficiency | |
| >99 % |
| >98.5 % |
| >97.5 % (including Active Interface Module) |
| >98.5 % |
Overvoltage category | III to EN 61800?5?1 |
Control method | Vector/Servo control with and without encoder or V/f control |
Fixed speeds | 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/PROFIBUS/PROFINET) |
Skippable speed ranges | 4, parameterizable |
Setpoint resolution | 0.001 rpm digital (14 bits + sign) 12 bits analog |
Braking operation | With Active Line Modules and Smart Line Modules, four-quadrant operation as standard (energy recovery). With Basic Line Modules, two-quadrant operation as standard, braking by means of an optional braking chopper, or alternatively by a Motor Module. |
Cabinet system |
Cabinet system | Rittal TS 8, doors with double-bit key, three-section base plates for cable entry |
Paint finish | RAL 7035 (indoor requirements) |
Mechanical specifications |
Degree of protection | IP20 (higher degrees of protection up to IP54 optional) |
Protection class | I acc. to EN 61800?5?1 |
Touch protection | EN 50274/BGV A3 for the intended purpose |
Cooling method | Forced air cooling AF according to EN 60146 |
Ambient conditions | Storage 2) | Transport 2) | Operation |
Ambient temperature | -25 ... +55 °C | -25 ... +70 °C from -40 °C for 24 hours | 0 ... +40 °C to +50 °C see derating data |
Relative humidity (condensation not permissible) | 5 ... 95 % Class 1K4 to IEC 60721?3?1 | 5 ... 95 % at 40 °C Class 2K3 acc. to IEC 60721?3?2 | 5 ... 95 % Class 3K3 acc. to IEC 60721?3?3 |
Environmental class/harmful chemical substances | Class 1C2 acc. to EN 60721?3?1 | Class 2C2 acc. to EN 60721?3?2 | Class 3C2 acc. to EN 60721?3?3 |
Organic/biological influences | Class 1B1 acc. to EN 60721?3?1 | Class 2B1 acc. to EN 60721?3?2 | Class 3B1 acc. to EN 60721?3?3 |
Degree of pollution | 2 acc. to EN 61800?5?1 |
Installation altitude | Cabinet Modules chassis format: ?2000 m above sea level - no derating; >2000 m, see characteristic curves/derating data For Booksize Cabinet Kit format Motor Modules as well as Central Braking Modules: ? 1000 m above sea level without derating, > 1000 m, see characteristic curves/derating data |
Mechanical stability | Storage 2) | Transport 2) | Operation |
Vibration load | Class 1M2 acc. to EN 60721?3?1 | Class 2M2 acc. to EN 60721?3?2 | – |
| 1.5 mm at 5 ... 9 Hz | 3.1 mm at 5 ... 9 Hz | 0.075 mm at 10 ... 58 Hz |
| 5 m/s? at >9 ... 200 Hz | 10 m/s? at >9 ... 200 Hz | 9.8 m/s? at >58 ... 200 Hz |
Shock load | Class 1M2 acc. to EN 60721?3?1 | Class 2M2 acc. to EN 60721?3?2 | Class 3M4 acc. to EN 60721?3?3 |
| 40 m/s? at 22 ms | 100 m/s? at 11 ms | 100 m/s? at 11 ms |
Compliance with standards |
Conformances/approvals, according to | CE (EMC Directive No. 2004/108/EC and Low Voltage Directive No. 2006/95/EC and Machinery Directive 2006/42/EC for functional safety) |
Radio interference suppression | SINAMICS drive converter systems are not designed for connection to the public grid (first environment). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800?3, "Second environment" (industrial networks). EMC disturbances can occur when connected to the public power networks. However, if additional measures are taken (e.g. > line filter), it can also be operated in the "first environment". |