Active Line Modules including Active Interface ModulesLine voltage 380 … 480 V 3 AC | Active Line Module |
|---|
Type |
|---|
6SL3730-7TE35-0BA3 | 6SL3730-7TE38-4BA3 | 6SL3730-7TE41-0BA3 | 6SL3730-7TE41-4BA3 |
|---|
For parallel connection, mounted to the left of the Line Connection Module |
|---|
6SL3730-7TE41-0BC3 | 6SL3730-7TE41-4BC3 |
|---|
Rated output | | | - at Irated DC (50 Hz 400 V)
| kW | 300 | 500 | 630 | 900 | | kW | 270 | 465 | 545 | 780 | - at Irated DC (60 Hz 460 V)
| hp | 500 | 700 | 900 | 1250 | | hp | 400 | 700 | 800 | 1000 | DC link current | | | | A | 549 | 940 | 1103 | 1574 | - Base-load current IH DC 1)
| A | 489 | 837 | 982 | 1404 | | A | 823 | 1410 | 1654 | 2361 | Infeed/regenerative feedback current | | | | A | 490 | 840 | 985 | 1405 | | A | 735 | 1260 | 1477 | 2107 | Power requirement | | | - 24 V DC aux. power supply
| A | 1.52 | 1.57 | 1.67 | 1.67 | | A | 1.8 | 3.6 | 5.4 | 5.4 | DC link capacitance | | | | ?F | 9600 | 16800 | 18900 | 28800 | | ?F | 76800 | 134400 | 230400 | 230400 | Power loss, max. 2) | | | | kW | 8.7 | 13.8 | 17.6 | 21.8 | | kW | 9.0 | 14.3 | 18.3 | 22.7 | Cooling air requirement | m3/s | 1.3 | 1.58 | 1.88 | 1.88 | Sound pressure level LpA 3) (1 m) at 50/60 Hz | dB | 72/74 | 77/79 | 78/80 | 78/80 | PE/GND connection | | PE bar | PE bar | PE bar | PE bar | | mm2 | 600 | 600 | 600 | 600 | - Conductor cross-section, max. (IEC)
| mm2 | 240 | 240 | 240 | 240 | Cable length, max. 4) | | | | m | 2700 | 3900 | 3900 | 3900 | | m | 4050 | 5850 | 5850 | 5850 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | mm | 1000 | 1200 | 1600 | 1600 | | mm | 2200 | 2200 | 2200 | 2200 | | mm | 600 | 600 | 600 | 600 | Weight, approx. | kg | 530 | 930 | 1360 | 1360 | Frame size | | GX + GI | HX + HI | JX + JI | JX + JI |
1) The base-load current IH DC is based on a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s. 2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 3) Total sound pressure level of Active Interface Module and Active Line Module. 4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. 5) The cabinet height increases by 250 mm with IP21 degree of protection, and by 400 mm with IP23 degree of protection.
|
|