dv/dt filters plus VPLLine voltage 380 ... 480 V 3 AC | dv/dt filter plus VPL | |
|---|
| 6SL3000-2DE35-0AA0 | 6SL3000-2DE38-4AA0 | 6SL3000-2DE41-4AA0 1) |
|---|
Ith max | A | 490 | 840 | 1450 | Degree of protection | | IP00 | IP00 | IP00 | Cable length, max. between dv/dt filter and motor | | | | | | m (ft) | 300 (984) | 300 (984) | 300 (984) | | m (ft) | 450 (1476) | 450 (1476) | 450 (1476) | Conformity | | CE | CE | CE | Approvals, acc. to | | cURus | cURus | cURus | dv/dt reactor | | | Power loss, max. | | | | | | kW | 0.874 | 1.106 | 1.111 | | kW | 0.904 | 1.115 | 1.154 | Connections | | | | | | | 1 ? hole for M12 | 1 ? hole for M12 | 1 ? hole for M12 | | | 1 ? hole for M12 | 1 ? hole for M12 | 1 ? hole for M12 | | | M6 screw | M6 screw | M6 screw | Dimensions | | | | | | mm (in) | 460 (18.1) | 460 (18.1) | 445 (17.5) | | mm (in) | 370 (14.6) | 385 (15.2) | 385 (15.2) | | mm (in) | 275 (10.8) | 312 (12.3) | 312 (12.3) | Weight, approx. | kg (lb) | 122 (269) | 149 (328) | 158 (348) | Voltage Peak Limiter (VPL) | | | Power loss, max. | | | | | | kW | 0.042 | 0.077 | 0.134 | | kW | 0.039 | 0.072 | 0.125 | Connections | | | | | | | 70 mm2 terminals | 1 x hole for M8 | 1 ? hole for M10 | | | 70 mm2 terminals | 1 x hole for M8 | 1 ? hole for M10 | | | 35 mm2 terminals | M8 stud | M8 stud | Dimensions | | | | | | mm (in) | 392 (15.4) | 309 (12.2) | 309 (12.2) | | mm (in) | 285 (11.2) | 1312.5 (51.7) | 1312.5 (51.7) | | mm (in) | 210 (8.27) | 400 (15.7) | 400 (15.7) | Weight, approx. | kg (lb) | 16 (35.3) | 48 (106) | 72 (159) | Suitable for PM330 Power Module | | 6SL3310-1PE33-0AA0 6SL3310-1PE33-7AA0 6SL3310-1PE34-6AA0 | 6SL3310-1PE35-8AA0 6SL3310-1PE36-6AA0 6SL3310-1PE37-4AA0 | 6SL3310-1PE38-4AA0 6SL3310-1PE38-8AA0 6SL3310-1PE41-0AA0 | | | GX | HX | JX |
1) Two dv/dt reactors are required for these dv/dt filters. The listed technical data refers to one dv/dt reactor. Line voltage 500 ... 690 V 3 AC | dv/dt filter plus VPL |
|---|
| 6SL3000-2DH38-1AA0 1) |
|---|
Ith max | A | 810 | Degree of protection | | IP00 | Cable length, max. between dv/dt filter and motor | | | | m (ft) | 300 (984) | | m (ft) | 450 (1476) | Conformity | | CE | Approvals, acc. to | | cURus | dv/dt reactor | Power loss, max. | | | | kW | 0.828 | | kW | 0.867 | Connections | | | | | 2 ? hole for M12 | | | 2 ? hole for M12 | | | M6 screw | Dimensions | | | | mm (in) | 445 (17.5) | | mm (in) | 385 (15.2) | | mm (in) | 312 (12.3) | Weight, approx. | kg (lb) | 160 (353) | Voltage Peak Limiter (VPL) | Power loss, max. | | | | kW | 0.106 | | kW | 0.1 | Connections | | | | | 1 x hole for M10 | | | 1 x hole for M10 | | | M8 stud | Dimensions | | | | mm (in) | 309 (12.2) | | mm (in) | 1312.5 (51.7) | | mm (in) | 400 (15.7) | Weight, approx. | kg (lb) | 72 (159) | Suitable for PM330 Power Module | | 6SL3310-1PG35-8AA0 6SL3310-1PG36-5AA0 6SL3310-1PG37-2AA0 | | | JX |
1) Two dv/dt reactors are required for these dv/dt filters. The listed technical data refers to one dv/dt reactor.
|
|