Derating data, PM240 Power ModulesPulse frequency
1) The pulse frequency can only be switched over from 4 kHz (default) to 2 kHz for the low overload (LO) duty cycle. Ambient temperature Low overload (LO) for PM240 Power Modules, frame size FSF High overload (HO) for PM240 Power Modules, frame size FSF Note: The operating temperature ranges of the Control Units should be taken into account. The temperature ranges are specified in the section Technical specifications under Control Units. Installation altitude Permissible line supplies depending on the installation altitude • Installation altitude up to 2000 m above sea level - Connection to every supply system permitted for the inverter • Installation altitudes between 2000 m and 4000 m above sea level - Connection to a TN system with grounded neutral point - TN systems with grounded line conductor are not permitted - The TN line system with grounded neutral point can also be supplied using an isolation transformer - The phase-to-phase voltage does not have to be reduced Note: The connected motors, power elements and components must be considered separately. Permissible output current as a function of the installation altitude for PM240 Power Modules, frame size FSF |
|||||||||||||||||||||||||||||||||