Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current | |
Current consumption, max. | 100 mA; 100 mA without loads at PG/OP socket; 130 mA load at PG/OP socket (5 V/90 mA); 200 mA load at PG/OP socket (24 V/100 mA) |
Interfaces | |
PROFIBUS DP | |
| 12 Mbit/s; 9.6 kbit/s to 12 Mbit/s |
Degree and class of protection | |
Degree of protection acc. to EN 60529 | |
| Yes |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C |
| 70 °C |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Extended ambient conditions | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method | |
Power supply | Terminal block |
Bus cables | 2 terminal blocks |
Dimensions | |
Width | 45 mm |
Height | 128 mm |
Depth | 67 mm |
Weights | |
Weight, approx. | 350 g |