MOTION-CONNECT connection systems
Current carrying capacity for power and signal cables

The current carrying capacity of PVC/PUR-insulated copper cables is specified for installation types B1, B2, C and E under continuous operating conditions in the table with reference to an ambient air temperature of 40 °C (104 °F). For other ambient temperatures, the values must be corrected by the derating factors from the table.

Cross-section

Current carrying capacity

rms AC 50/60 Hz or DC in amps for installation type

 

B1

B2

C

E

mm2

Single-core cables in protection tubes or installation ducts

Multi-core cables in protection tubes or installation ducts

Multi-core cables, vertically or horizontally on walls/open, without protection tubes and installation ducts/with contact

Multi-core cables, horizontally or vertically on perforated cable racks/open, without protection tubes and installation ducts/with contact

Electronics1)

    

0.20

4.3

4.4

4.4

0.50

7.5

7.5

7.8

0.75

9

9.5

10

Power2)

    

0.75

8.6

8.5

9.8

10.4

1.00

10.3

10.1

11.7

12.4

1.50

13.5

13.1

15.2

16.1

2.50

18.3

17.4

21

22

4

24

23

28

30

6

31

30

36

37

10

44

40

50

52

16

59

54

66

70

25

77

70

84

88

35

96

86

104

110

50

117

103

125

133

70

149

130

160

171

95

180

165

194

207

120

208

179

225

240



1) One control circuit pair.

2) One symmetrically loaded three-phase AC cable.

Derating factors for power and signal cables

Ambient air temperature
°C (°F)

Derating factor

according to EN 60204-1, Table D.1

30 (86)

1.15

35 (95)

1.08

40 (104)

1.00

45 (113)

0.91

50 (122)

0.82

55 (131)

0.71

60 (140)

0.58