General information | | | |
Product type designation | PS 25W 24VDC | PS 60W 24/48/60V DC | PS 60W 120/230V AC/DC |
Engineering with | | | |
| V12 / V12 | V12 / V12 | V12 / V12 |
| V5.5 SP3 or higher | V5.5 SP3 or higher | V5.5 SP3 or higher |
Supply voltage | | | |
Rated value (DC) | 24 V | 24 V / 48 V / 60 V | 120 V / 230 V |
permissible range, lower limit (DC) | Static 19.2 V, dynamic 18.5 V | Static 19.2 V, dynamic 18.5 V | 88 V |
permissible range, upper limit (DC) | Static 28.8 V, dynamic 30.2 V | Static 72 V, dynamic 75.5 V | 300 V |
Rated value (AC) | | | 120 V / 230 V |
permissible range, lower limit (AC) | | | 85 V |
permissible range, upper limit (AC) | | | 264 V |
Reverse polarity protection | Yes | Yes | |
Short-circuit protection | Yes | Yes | Yes |
Line frequency | | | |
| | | Yes |
| | | 47 Hz |
| | | 63 Hz |
Mains buffering | | | |
| 20 ms | 20 ms | 20 ms |
Input current | | | |
Rated value at 24 V DC | 1.3 A | 3 A | |
Rated value at 48 V DC | | 1.5 A | |
Rated value at 60 V DC | | 1.2 A | |
Rated value at 120 V DC | | | 0.6 A |
Rated value at 230 V DC | | | 0.3 A |
Rated value at 120 V AC | | | 0.6 A |
Rated value at 230 V AC | | | 0.34 A |
Output current | | | |
Short-circuit protection | Yes | Yes | Yes |
Power | | | |
Infeed power to the backplane bus | 25 W | 60 W | 60 W |
Power loss | | | |
Power loss at nominal rating conditions | 6.2 W | 12 W | 12 W |
Interrupts/diagnostics/status information | | | |
Status indicator | Yes | Yes | Yes |
Potential separation | | | |
primary/secondary | Yes | Yes; Electrical isolation for 230 V AC (reinforced isolation) | Yes |
Isolation | | | |
Isolation tested with | 707 V DC (type test) | 2 500 V DC/2 s (routine test) | 2 500 V DC/2 s (routine test) |
EMC | | | |
Interference immunity against voltage surge | | | |
| Yes; +/- 1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), +/- 2 kV (acc. to IEC 61000-4-5; 1995; surge asymm.), no external protective circuit required | Yes; +/- 1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), +/- 2 kV (acc. to IEC 61000-4-5; 1995; surge asymm.), no external protective circuit required | Yes; +/- 1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), +/- 2 kV (acc. to IEC 61000-4-5; 1995; surge asymm.), no external protective circuit required |
Degree and class of protection | | | |
Degree of protection acc. to EN 60529 | IP20 | IP20 | IP20 |
Protection class | 3; with protective conductor | 1; with protective conductor | 1; with protective conductor |
Dimensions | | | |
Width | 35 mm | 70 mm | 70 mm |
Height | 147 mm | 147 mm | 147 mm |
Depth | 129 mm | 129 mm | 129 mm |
Weights | | | |
Weight, approx. | 350 g | 600 g | 600 g |