A converter must always be connected to the line supply through a commutation inductance. This must have at least 4 % uK! The commutation inductance can be in the form of a converter transformer or, for the appropriate line supply, in the form of a commutating reactor.
A line supply can be considered to be "stiff" if the power ratio Ps/Sk ? 0.01. Even for stiff line supplies, the commutation inductance must have a uK of at least 4 %!
For high-rating converters, the line reactance, i.e. the finite fault level (short-circuit power) of the line supply must be taken into account; this also results in higher uK values. Recommendation for the ratio of the line supply fault level (short-circuit power) to the apparent drive power > 33:1.
The commutating reactors are dimensioned according to the rated motor current in the armature or field circuit.
Operation with line frequencies of 50 Hz and 60 Hz
The rated currents ILn of the reactors, specified in the table, apply for operation with a line frequency f = 50 Hz. It is permissible to operate the reactors with a line frequency f = 60 Hz. In this case, the next-higher voltage level must be selected (e.g. 480 V instead of 400 V).
At the same time, the voltage drop ?V increases by 8 %.
Arrangement of reactors and radio interference suppression filters
(1) The commutating reactor in the field circuit is dimensioned for the rated motor field current.
(2) The commutating reactor in the armature circuit is dimensioned for the rated motor armature current. The line current is 0.82 times the DC current.
(3) The radio interference suppression filter for the armature circuit is dimensioned for the rated motor armature current. The line current is 0.82 times the DC current.
(4) The radio interference suppression filter for the field circuit is dimensioned for the rated motor field current.
(5) The electronics power supply itself does not require a radio interference suppression filter. Current consumption 1 A at 400 V, 2 A at 230 V.
(6) If the power supply voltages for the armature circuit, field circuit and electronics power supply are the same, then the voltage for the field and electronics power supply can also be taken after the radio interference suppression filter for the armature circuit.
1)
1) All commutating reactors with rated voltages VN ? 600 V to UL
Note: The commutating reactors are dimensioned according to the rated motor current in the armature and field circuits. When the unit is connected to a single phase, single-phase commutating reactors must also be used in the armature circuit. These are available on request.
The tables below list the commutating reactors which are available as standard. Additional information can be found in the Operating Instructions "SINAMICS DCM Commutation reactors" (see http://support.automation.siemens.com/WW/view/en/85062393).
General technical specifications
Degree of protection
IP00
Protection class
Class 1 2)
Cooling
AN, self-ventilated
Inductance tolerance
± 10 %
Environmental classes according to DIN IEC 60721-3, Parts 1 to 3
Climatic:
Storage: 1K3
Transport: 2K2
Operation: 3K3
Mechanical: 3M3
Ambient temperature during operation
1-phase reactors
0 to +45 °C, above with derating
3-phase reactors
0 to +40 °C, above with derating
Ambient temperature for storage and transport
-40 to +70 °C
Installation altitude (at rated current)
? 1000 m above sea level, above with derating
Operation at 50 Hz and 60 Hz with rated current is permissible
2) Note about protection class 1: Despite protective conductor connection, no 'touchable conductive parts' with regard to the standard (e.g. EN 61800-5-1) are defined. In this case, the protective conductor ensures that no dangerous voltages/currents can act at the mounting surfaces. The complete reactor must be considered as being an active component.
Three-phase commutating reactors, uK = 4 %
AC rated current
Inductance
Copper losses
Total losses
Short-circuit current rating (SCCR)
Weight
Rated insulation voltage
Article No.
A
mH
W
W
kA
kg
V
Rated voltage 400 V
13
2.315
22.8
33.1
2.0 (20 ms)
2.9
600
6RX1800-4DK00
25
1.158
30.8
53.2
5.0 (20 ms)
4.4
600
6RX1800-4DK01
51
0.579
43.5
73.2
6.5 (100 ms)
10.9
600
6RX1800-4DK02
76
0.386
64.4
118.5
9.0 (100 ms)
13.8
600
6RX1800-4DK03
106
0.278
51.3
119.3
15 (100 ms)
23.9
600
6RX1800-4DK04
174
0.169
164.8
206.4
15 (100 ms)
24.0
600
6RX1800-4DK05
232
0.127
197.4
256.2
20 (100 ms)
26.8
600
6RX1800-4DK06
332
0.089
190.7
251.1
24 (200 ms)
45.8
600
6RX1800-4DK07
374
0.079
186.7
251.7
24 (200 ms)
56.8
600
6RX1800-4DK08
498
0.059
277.0
357.4
35 (200 ms)
60.0
600
6RX1800-4DK10
706
0.042
329.4
424.8
55 (200 ms)
81.6
1000
6RX1800-4DK11
996
0.030
390.3
562.8
75 (200 ms)
100.1
1000
6RX1800-4DK12
1328
0.022
339.3
554.5
75 (200 ms)
138.8
1000
6RX1800-4DK13
1660
0.018
369.3
591.9
75 (200 ms)
210.7
1000
6RX1800-4DK14
2490
0.012
587.3
1038.3
75 (200 ms)
205.6
1000
6RX1800-4DK15
Note: Commutating reactors with uK = 2 % are available on request. A limited tolerance range is also possible for parallel connections.
Three-phase commutating reactors, uK = 4 %
AC rated current
Inductance
Copper losses
Total losses
Short-circuit current rating (SCCR)
Weight
Rated insulation voltage
Article No.
A
mH
W
W
kA
kg
V
Rated voltage 480 V
13
2.779
27.4
39.2
2.0 (20 ms)
2.9
600
6RX1800-4FK00
25
1.389
34.8
57.8
5.0 (20 ms)
6.0
600
6RX1800-4FK01
51
0.695
42.3
77.2
6.5 (100 ms)
11.8
600
6RX1800-4FK02
76
0.463
56.3
118.0
9.0 (100 ms)
16.3
600
6RX1800-4FK03
106
0.333
68.8
152.9
15 (100 ms)
22.3
600
6RX1800-4FK04
174
0.202
204.6
255.6
15 (100 ms)
26.0
600
6RX1800-4FK05
232
0.152
178.3
231.5
20 (100 ms)
37.8
600
6RX1800-4FK06
332
0.106
193.7
261.5
24 (100 ms)
56.1
600
6RX1800-4FK07
374
0.094
189.1
279.2
24 (100 ms)
56.8
600
6RX1800-4FK08
498
0.071
313.8
396.9
35 (200 ms)
78.1
1000
6RX1800-4FK10
664
0.053
255.6
360.8
75 (200 ms)
96.6
1000
6RX1800-4FK11
706
0.050
293.9
404.1
75 (200 ms)
96.6
1000
6RX1800-4FK12
913
0.039
375.6
558.6
75 (200 ms)
114.5
1000
6RX1800-4FK13
996
0.035
332.7
532.8
75 (200 ms)
127.8
1000
6RX1800-4FK14
1328
0.027
320.4
573.7
75 (200 ms)
177.6
1000
6RX1800-4FK15
1660
0.021
436.5
819.0
75 (200 ms)
161.0
1000
6RX1800-4FK16
1826
0.019
464.7
819.9
75 (200 ms)
164.2
1000
6RX1800-4FK17
2324
0.015
671.8
1056.7
75 (200 ms)
258.2
1000
6RX1800-4FK18
Rated voltage 575 V
51
0.832
56.8
109.7
6.5 (100 ms)
13.6
600
6RX1800-4GK00
106
0.399
65.5
156.7
15 (100 ms)
26.4
600
6RX1800-4GK01
174
0.243
150.0
200.5
15 (100 ms)
34.5
600
6RX1800-4GK02
332
0.127
252.1
327.3
24 (200 ms)
63.1
600
6RX1800-4GK03
498
0.085
330.3
427.5
35 (200 ms)
86.0
1000
6RX1800-4GK04
598
0.071
339.6
455.5
55 (200 ms)
89.8
1000
6RX1800-4GK05
631
0.067
322.8
441.1
55 (200 ms)
95.7
1000
6RX1800-4GK06
664
0.064
380.7
547.2
75 (200 ms)
108.4
1000
6RX1800-4GK07
706
0.060
392.7
564.5
75 (200 ms)
120.6
1000
6RX1800-4GK08
830
0.051
308.1
498.3
75 (200 ms)
134.8
1000
6RX1800-4GK10
913
0.046
320.7
515.9
75 (200 ms)
143.9
1000
6RX1800-4GK11
1245
0.034
371.4
605.4
75 (200 ms)
206.1
1000
6RX1800-4GK12
1328
0.032
503.1
812.4
75 (200 ms)
160.9
1000
6RX1800-4GK13
1660
0.025
631.3
993.1
75 (200 ms)
202.0
1000
6RX1800-4GK14
1826
0.023
614.7
1006.9
75 (200 ms)
212.1
1000
6RX1800-4GK15
2158
0.020
534.6
1073.7
75 (200 ms)
303.0
1000
6RX1800-4GK16
2324
0.018
556.2
1110.0
75 (200 ms)
321.6
1000
6RX1800-4GK17
Note: Commutating reactors with uK = 2 % are available on request. A limited tolerance range is also possible for parallel connections.
Three-phase commutating reactors, uK = 4 %
AC rated current
Inductance
Copper losses
Total losses
Short-circuit current rating (SCCR)
Weight
Rated insulation voltage
Article No.
A
mH
W
W
kA
kg
V
Rated voltage 690 V
598
0.085
388.2
562.1
55 (200 ms)
108.9
1000
6RX1800-4KK00
631
0.080
402.0
586.4
75 (200 ms)
113.3
1000
6RX1800-4KK01
789
0.064
362.7
564.6
75 (200 ms)
141.9
1000
6RX1800-4KK02
830
0.061
350.7
561.4
75 (200 ms)
153.4
1000
6RX1800-4KK03
1245
0.041
505.2
845.7
75 (200 ms)
169.7
1000
6RX1800-4KK04
1577
0.032
716.8
1093.8
75 (200 ms)
226.1
1000
6RX1800-4KK05
1660
0.031
596.0
1011.8
75 (200 ms)
257.2
1000
6RX1800-4KK06
2158
0.024
484.8
1185.6
75 (200 ms)
360.2
1000
6RX1800-4KK07
Rated voltage 830 V
789
0.077
312.0
532.1
75 (200 ms)
205.2
1000
6RX1800-4LK00
1245
0.049
692.4
1061.9
75 (200 ms)
222.4
1000
6RX1800-4LK01
1577
0.039
479.4
1059.6
75 (200 ms)
308.5
1000
6RX1800-4LK02
1826
0.033
585.6
1269.0
75 (200 ms)
372.5
1000
6RX1800-4LK03
Rated voltage 950 V
1826
0.038
534.9
1303.5
75 (200 ms)
399.7
1000
6RX1800-4MK00
Note: Commutating reactors with uK = 2 % are available on request. A limited tolerance range is also possible for parallel connections.